{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000417704","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000417704","canonicalUrl":"https://aoctrl.com/abb/3AXD50000417704","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000417704","rawCanonicalId":null},"summary":{"shortDescription":"ABB, ACH580 series, LV AC wall-mounted drive for HVAC, 7.5 kW, 31.2 A, 200-240 V, 3-phase, IP21, BACnet.","salesMarkdown":"The 3AXD50000417704: Normal-use (Pn) is 7.5 kW with 31.2 A output — that's the continuous rating for typical pump/fan loads. Light-overload (PlD) matches the normal-use kW at 30.8 A, so you get the same power headroom but slightly lower current limit for variable-torque HVAC duty. Pick the duty class that matches your load profile; the drive is rated for all three. ## Inputs, outputs, and fieldbus Built-in BACnet communication — no extra gateway needed for BMS integration. Two analog inputs and two analog outputs cover setpoint and feedback loops; six digital inputs and three digital outputs handle start/stop, fault reset, and status. That's enough I/O for a standalone AHU or pump skid without an expansion module. Industrial Ethernet hardware count is zero, so BACnet MS/TP over RS-485 is the wired option here. Wall-mount frame size R2, IP21 with NEMA Type 1 enclosure — fine for indoor electrical rooms and mechanical plant rooms where drips and dust aren't heavy. Ambient temperature max 40 °C, altitude 1000 m without derating, 95% RH. Standby loss is 14 W, so the drive doesn't cook the cabinet when the motor's off. Sound level 64 dB(A) — noticeable but not shouting in a machine room.","metaTitle":"3AXD50000417704 ABB ACH580-01-032A-2 LV AC Drive, 7.5 kW, 31","metaDescription":"ABB ACH580-01-032A-2 LV AC wall-mounted drive, 7.5 kW / 31.2 A normal use, 200-240 V 3-phase, IP21, BACnet, active production, RoHS/REACH compliant.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"SCIP":"8e2f57c3-6325-4d67-b705-81477a8d922e Finland","Altitude":"1000 m","Includes":"Control unit","Frame Size":"R2","Sound dB (A)":"64 dB(A)","Standby Loss":"14 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP21","Apparent Power Output":"12 kV·A","Communication Protocol":"BACNET","Power Consumption (@Pcons)":"359 W","Operating Humidity (RHamβ)":"95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"7.5 kW","Output Current, Normal Use (In)":"31.2 A","Output Power, Heavy-Duty Use (PhD)":"5.5 kW","Output Current, Heavy-Duty Use (IhD)":"24.2 A","Output Power, Light-Overload Use (PlD)":"7.5 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"30.8 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000417704","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000417704/alternatives.json"},"ai":{"faq":[{"question":"What are the key power ratings for this drive?","answer":"Normal-use output is 7.5 kW at 31.2 A; heavy-duty is 5.5 kW at 24.2 A; light-overload matches 7.5 kW at 30.8 A. Input is 200-240 V three-phase, 47.5-63 Hz."},{"question":"What communication protocol does the 3AXD50000417704 support?","answer":"BACnet is the listed protocol — no Industrial Ethernet interfaces on this variant, so BACnet MS/TP over RS-485 is the connection method."},{"question":"What compliance documentation does ABB provide for this drive?","answer":"RoHS compliance dated 2024-05-08 per EU Directive 2011/65/EU, REACH declaration dated 2025-09-05 confirming substances above 0.1 mass percent, and SCIP number 8e2f57c3-6325-4d67-b705-81477a8d922e Finland."},{"question":"What is the enclosure rating and mounting for the 3AXD50000417704?","answer":"IP21 / NEMA Type 1, wall-mounted, frame size R2. Ambient temperature max 40 °C, altitude 1000 m, humidity 95% RH."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000417704","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000417704 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}