{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000417810","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000417810","canonicalUrl":"https://aoctrl.com/abb/3AXD50000417810","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000417810","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 series, LV AC wall-mounted HVAC drive, 1.5 kW / 7.6 A normal use, 200–240 V 3-phase, IP55, BACnet, frame R1.","salesMarkdown":"The 3AXD50000417810: BACnet MS/TP is the onboard protocol, with two analog inputs and two analog outputs for sensor feedback or setpoint control. No industrial Ethernet port here — this is a pure BACnet drive for BMS integration. Enclosure is IP55 / NEMA 12, so it handles hose-down washdown and dusty plant floors. Ambient limit is 40 °C, which covers most mechanical rooms but derate if the panel sits in a hot attic. ## Duty ratings — normal, heavy, light Three output current curves cover the load profile: normal use 7.6 A (1.5 kW), heavy-duty 6.6 A (1.1 kW), and light-overload 7.5 A (1.5 kW). Lifecycle status is active — no end-of-life notice, no last-time-buy pressure. RoHS compliance dated 2024-05-08 and REACH compliance dated 2025-09-05 are on file. The SCIP number (12216470-2923-46fb-9b3c-c7084d490da0 Finland) is registered for EU waste reporting. ## I/O and auxiliaries Six digital inputs and three digital outputs cover start/stop, fault reset, and status feedback for a typical fan or pump. The onboard lithium coin cell (CR2032, 220 mAh) keeps the real-time clock alive through power loss. Standby loss is 13 W; full-load power consumption is 82 W.","metaTitle":"ABB 3AXD50000417810 ACH580 HVAC Drive, 1.5 kW, 7.6 A","metaDescription":"Active ABB ACH580-01 wall-mounted drive, 1.5 kW normal use, 7.6 A output, 200-240 V 3-phase, IP55, BACnet, RoHS/REACH compliant. Source via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"SCIP":"12216470-2923-46fb-9b3c-c7084d490da0 Finland","Includes":"With control unit","Frame Size":"R1","Standby Loss":"13 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP55","Apparent Power Output":"3.0 kV·A","Communication Protocol":"BACNET","Power Consumption (@Pcons)":"82 W","Operating Humidity (RHamβ)":"95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"1.5 kW","Output Current, Normal Use (In)":"7.6 A","Output Power, Heavy-Duty Use (PhD)":"1.1 kW","Output Current, Heavy-Duty Use (IhD)":"6.6 A","Output Power, Light-Overload Use (PlD)":"1.5 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"7.5 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000417810","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000417810/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation is available for this drive?","answer":"RoHS compliance dated 2024-05-08 and REACH compliance dated 2025-09-05 are on file. The SCIP number 12216470-2923-46fb-9b3c-c7084d490da0 Finland is registered for EU waste reporting."},{"question":"What are the key ratings for normal and heavy-duty use?","answer":"Normal use: 1.5 kW at 7.6 A. Heavy-duty: 1.1 kW at 6.6 A. Light-overload: 1.5 kW at 7.5 A."},{"question":"Does this drive include the control unit?","answer":"Yes, it ships with the control unit included — no separate ordering needed."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000417810","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000417810 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}