{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000417865","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000417865","canonicalUrl":"https://aoctrl.com/abb/3AXD50000417865","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000417865","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 series, LV AC wall-mounted HVAC drive, 3AXD50000417865, 11 kW / 47 A normal duty, 200–240 V 3-phase, IP55, BACnet, frame R3.","salesMarkdown":"The 3AXD50000417865: The 47 A normal-use output current is the figure to size branch protection and cabling for continuous fan/pump duty. If your application cycles at heavy overload (e.g. high-torque start or rapid deceleration), the 30.8 A heavy-duty rating governs — stay within that for the rated overload profile. Light-overload use at 46.2 A gives a narrow margin above heavy duty but still below normal. Input voltage is 200…240 V, 3-phase, 47.5…63 Hz — confirm your line side matches before committing. Enclosure is IP55 / NEMA Type 12, wall-mounted, frame R3. That means it handles dust and hose-down in HVAC mechanical rooms or light industrial washdown areas. Ambient temperature max is 40 °C, humidity up to 95% RH. The standby loss of 15 W is low enough to ignore in most panel heat calculations. Two analog inputs and two analog outputs are on board; six digital inputs and three digital outputs handle start/stop, fault reset, and speed reference. BACnet is the native fieldbus — no option card needed for BMS integration. No Industrial Ethernet interface is fitted; if you need Modbus TCP or PROFINET, that is a different variant.","metaTitle":"ABB 3AXD50000417865 ACH580-01 HVAC Drive, 11 kW, 47 A","metaDescription":"ABB 3AXD50000417865 ACH580-01 wall-mounted drive, 11 kW / 47 A normal duty, 230 V 3-phase, IP55, BACnet, active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"SCIP":"2f1b7d72-3cb1-49a1-82e4-a721459937d4 Finland","Includes":"With control unit","Frame Size":"R3","Standby Loss":"15 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP55","Apparent Power Output":"19 kV·A","Communication Protocol":"BACNET","Power Consumption (@Pcons)":"533 W","Operating Humidity (RHamβ)":"95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"11 kW","Output Current, Normal Use (In)":"47 A","Output Power, Heavy-Duty Use (PhD)":"7.5 kW","Output Current, Heavy-Duty Use (IhD)":"30.8 A","Output Power, Light-Overload Use (PlD)":"11.0 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"46.2 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000417865","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000417865/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation is available for this drive?","answer":"RoHS compliance per EU Directive 2011/65/EU and Amendment 2015/863 is declared. REACH declaration confirms substances above 0.1% mass are present. The SCIP number is 2f1b7d72-3cb1-49a1-82e4-a721459937d4 Finland. WEEE category 5 applies."},{"question":"What are the key output ratings for normal, heavy, and light overload?","answer":"Normal-use output is 11 kW / 47 A; heavy-duty use is 7.5 kW / 30.8 A; light-overload use is 11.0 kW / 46.2 A. The heavy-duty figure governs for high-torque or cyclic loads."},{"question":"What is the SCIP number for this drive?","answer":"The SCIP number is 2f1b7d72-3cb1-49a1-82e4-a721459937d4 Finland."},{"question":"Does this drive include the control unit?","answer":"Yes, the drive is supplied with the control unit included."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000417865","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000417865 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}