{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000417902","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000417902","canonicalUrl":"https://aoctrl.com/abb/3AXD50000417902","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000417902","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 wall-mounted HVAC drive, 3AXD50000417902, 37 kW normal use, 144 A, 200-240 V, IP55, BACnet, frame R6.","salesMarkdown":"The ABB 3AXD50000417902 is a wall-mounted HVAC drive rated for 37 kW normal use at 144 A on a 200-240 V three-phase supply. It ships with the control unit included and communicates over BACnet. Normal-use output current is 144 A; heavy-duty use drops to 114 A at 30.0 kW. That spread tells you the drive is sized for a constant-torque HVAC fan or pump load — the heavy-duty figure governs if you need headroom for a variable-torque profile or a motor that occasionally overloads. Light-overload use matches the normal-use current at 143 A, so the drive doesn't force a derating for standard building loads. Standby loss is 22 W, which matters for energy-code compliance in continuously occupied mechanical rooms. The IP55 enclosure and NEMA Type12 rating mean it handles dust and hose-down cleaning without a separate cabinet — wall-mount it directly in the equipment room. Two analog inputs and two analog outputs are on board — enough for a speed reference and feedback from a pressure or temperature transmitter. Six digital inputs and three digital outputs handle start/stop, fault reset, and status indication. There is no Industrial Ethernet port; BACnet is the only fieldbus, so if the BMS speaks BACnet MS/TP, this drive connects directly without a gateway.","metaTitle":"ABB 3AXD50000417902 ACH580 HVAC Drive, 37 kW, 144 A, IP55","metaDescription":"ABB ACH580-01 wall-mounted drive, 37 kW normal use, 144 A, 200-240 V, IP55, BACnet, active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"SCIP":"17a7c876-3c0e-4fce-930a-1904c59b53dd Finland","Includes":"With control unit","Frame Size":"R6","Standby Loss":"22 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP55","Apparent Power Output":"57 kV·A","Communication Protocol":"BACNET","Power Consumption (@Pcons)":"1932 W","Operating Humidity (RHamβ)":"95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"37 kW","Output Current, Normal Use (In)":"144 A","Output Power, Heavy-Duty Use (PhD)":"30.0 kW","Output Current, Heavy-Duty Use (IhD)":"114 A","Output Power, Light-Overload Use (PlD)":"37 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"143 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000417902","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000417902/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation is available for this drive?","answer":"RoHS compliance per EU Directive 2011/65/EU and Amendment 2015/863 (dated 20240508), REACH declaration (dated 20250905) noting substances above 0.1 mass percentage, and SCIP number 17a7c876-3c0e-4fce-930a-1904c59b53dd Finland under WEEE Category 4."},{"question":"What are the key ratings for this drive?","answer":"Normal use: 37 kW, 144 A. Heavy-duty use: 30.0 kW, 114 A. Input 200-240 V three-phase, 47.5-63 Hz. IP55, NEMA Type12, IE2 efficiency. Standby loss 22 W."},{"question":"Does this drive include a control unit?","answer":"Yes, the listing includes the control unit as part of the order code."},{"question":"What fieldbus protocol does it support?","answer":"BACnet is the listed communication protocol. There is no Industrial Ethernet port."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000417902","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000417902 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}