{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000417926","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000417926","canonicalUrl":"https://aoctrl.com/abb/3AXD50000417926","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000417926","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 wall-mounted HVAC drive, 3-phase 200–240 V, 55 kW normal use, 213 A, IP55, NEMA Type12, BACnet, frame R7, with control unit.","salesMarkdown":"The ABB 3AXD50000417926 is a wall-mounted HVAC drive rated for 55 kW normal use (213 A) on a 200–240 V three-phase supply. It ships with the control unit included, frame size R7, and carries IP55 / NEMA Type12 protection. The 22 W standby loss matters for energy-code compliance when the fan isn't calling. Three duty points: normal use 55 kW / 213 A, heavy-duty 45 kW / 169 A, light-overload 55 kW / 211 A. Input voltage is 200–240 V, frequency range 47.5–63 Hz. Efficiency is IE2, which is the baseline for HVAC drives in most markets — not premium, but meets the minimum for the application class. Ambient max is 40 °C; above that you'd derate the output current. ## I/O and network Two analog inputs and two analog outputs are onboard — enough for a speed reference and feedback from a duct static-pressure sensor. Digital I/O counts six inputs and three outputs, which covers start/stop, fault reset, and a run-status relay. The built-in BACnet protocol means it talks directly to a building management system without a gateway card. No industrial Ethernet interface is fitted, so if you need Modbus TCP or PROFINET, that's an option slot.","metaTitle":"ABB 3AXD50000417926 ACH580-01 HVAC Drive, 55 kW, 213 A, 230","metaDescription":"Active-production ABB ACH580-01 wall-mounted HVAC drive, 55 kW normal use, 213 A, 230 V input, IP55, NEMA 12, BACnet, IE2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"SCIP":"dc827d29-312d-433e-afb4-0816392e0848 Finland","Includes":"With control unit","Frame Size":"R7","Standby Loss":"22 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP55","Apparent Power Output":"85 kV·A","Communication Protocol":"BACNET","Power Consumption (@Pcons)":"2854 W","Operating Humidity (RHamβ)":"95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"55 kW","Output Current, Normal Use (In)":"213 A","Output Power, Heavy-Duty Use (PhD)":"45 kW","Output Current, Heavy-Duty Use (IhD)":"169 A","Output Power, Light-Overload Use (PlD)":"55 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"211 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000417926","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000417926/alternatives.json"},"ai":{"faq":[{"question":"What is the SCIP number for this drive?","answer":"The SCIP number is dc827d29-312d-433e-afb4-0816392e0848 Finland."},{"question":"Does the drive include a control unit?","answer":"Yes, it ships with the control unit included."},{"question":"What compliance documentation is available?","answer":"RoHS compliance follows EU Directive 2011/65/EU and Amendment 2015/863 (date 20240508). REACH declaration confirms substances > 0.1 mass percentage (date 20250905). WEEE category 4 applies."},{"question":"What are the key ratings for normal and heavy-duty use?","answer":"Normal use: 55 kW, 213 A. Heavy-duty use: 45 kW, 169 A. Light-overload use: 55 kW, 211 A. Input voltage 200–240 V three-phase."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000417926","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000417926 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}