{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000418022","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000418022","canonicalUrl":"https://aoctrl.com/abb/3AXD50000418022","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000418022","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ580-01-060A-2, 3AXD50000418022, LV AC wall-mounted drive, 15 kW normal use, 60 A output current, 200-240 V 3-phase, IP21, NEMA 1, frame R3.","salesMarkdown":"The ABB ACQ580-01-060A-2 (3AXD50000418022) is a wall-mounted LV AC drive rated for 15 kW normal use (60 A output) on a 200-240 V three-phase supply, frame size R3. It's built for water and wastewater duty, with a heavy-duty rating of 11 kW (46.2 A) and light-overload rating of 15 kW (59 A). The drive includes the control unit, has two analog inputs and two analog outputs, six digital inputs and three digital outputs, and communicates via CAN. Efficiency is IE2, power factor is 0.98, standby loss is 15 W, and it's rated for ambient temperatures up to 40 °C, IP21, NEMA 1. The operating frequency range is 47.5-63 Hz, and it can be installed at altitudes up to 4000 m. ## Integration notes Wall-mounted, frame R3, IP21, NEMA 1 — suitable for indoor clean environments. The drive has no industrial Ethernet interface (0 hardware interfaces for Ethernet), so plan for CAN communication or a separate gateway if Ethernet is needed. The battery is a CR2032 lithium coin cell (220 mAh, 3 V) for the real-time clock. Sound level is 76 dB(A) — noticeable in a quiet control room. Power consumption at rated load is 781 W, with 15 W standby loss. Apparent power output is 24 kVA. Operating humidity range is 5-95% non-condensing.","metaTitle":"ABB 3AXD50000418022 ACQ580-01-060A-2 Drive, 15 kW, 60 A","metaDescription":"ABB ACQ580-01-060A-2 LV AC wall-mounted drive, 15 kW normal use, 60 A output, 200-240 V 3-phase, IP21, NEMA 1, active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"SCIP":"f1c9bd3a-ea8b-410d-bd78-7d4098ee31cf Finland","Altitude":"4000 m","Includes":"Control unit","Frame Size":"R3","Power Factor":"0.98","Sound dB (A)":"76 dB(A)","Standby Loss":"15 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP21","Apparent Power Output":"24 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"781 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"15 kW","Output Current, Normal Use (In)":"60 A","Output Power, Heavy-Duty Use (PhD)":"11 kW","Output Current, Heavy-Duty Use (IhD)":"46.2 A","Output Power, Light-Overload Use (PlD)":"15 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"59 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000418022","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000418022/alternatives.json"},"ai":{"faq":[{"question":"What is the SCIP number for this drive?","answer":"The SCIP number is f1c9bd3a-ea8b-410d-bd78-7d4098ee31cf Finland."},{"question":"What is the altitude rating of this drive?","answer":"It is rated for installation at altitudes up to 4000 m."},{"question":"What compliance documentation is available for 3AXD50000418022?","answer":"RoHS compliance follows EU Directive 2011/65/EU and Amendment 2015/863 (date 20240508). REACH compliance date is 20250905, and the product contains substances above 0.1% mass percentage. The SCIP number is f1c9bd3a-ea8b-410d-bd78-7d4098ee31cf Finland."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000418022","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000418022 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}