{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000418145","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000418145","canonicalUrl":"https://aoctrl.com/abb/3AXD50000418145","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000418145","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ580-01 LV AC wall-mounted drive, 5.5 kW / 24.5 A, 200-240 V 3-phase, IP55, NEMA Type 12, Frame R2.","salesMarkdown":"## Enclosure, mounting, and environment The 3AXD50000418145: IP55 and NEMA Type 12 — this drive is built for washdown zones and dusty indoor locations. Wall-mounted in Frame R2, it fits a standard backplate layout. Rated for altitudes up to 4000 m, so it works in high-desert or mountain installations without a special derate. Ambient max is 40 °C; keep the cooling air path clear and the 64 dB(A) sound level in mind if it goes into a quiet control room. Two analog inputs and two analog outputs for process signals — pressure, flow, level transmitters on the input side, speed or torque reference on the outputs. Six digital inputs and three digital outputs handle start/stop, fault reset, and status feedback. Communication is CAN-based; no onboard Ethernet, so if you need Modbus TCP or PROFINET, plan for an external gateway or option module. ## Efficiency and standby IE2 efficiency class at 0.98 power factor. Standby loss is 14 W — negligible for energy accounting but worth noting if the drive is on a UPS-backed circuit. Power consumption at rated load is 255 W.","metaTitle":"ABB 3AXD50000418145 ACQ580-01 Drive, 5.5 kW, 24.5 A","metaDescription":"ABB ACQ580-01 wall-mounted drive, 5.5 kW normal-use output, 24.5 A, IP55, NEMA 12. Active production. Sourced to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"SCIP":"cf2353ee-9777-4c0e-a5fb-5527ed389255 Finland","Altitude":"4000 m","Includes":"Control unit","Frame Size":"R2","Power Factor":"0.98","Sound dB (A)":"64 dB(A)","Standby Loss":"14 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP55","Apparent Power Output":"9.8 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"255 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"5.5 kW","Output Current, Normal Use (In)":"24.5 A","Output Power, Heavy-Duty Use (PhD)":"4 kW","Output Current, Heavy-Duty Use (IhD)":"16.7 A","Output Power, Light-Overload Use (PlD)":"5.5 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"24.2 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000418145","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000418145/alternatives.json"},"ai":{"faq":[{"question":"What is the maximum altitude rating?","answer":"Rated for installation at altitudes up to 4000 m without derating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000418145","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000418145 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}