{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000418237","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000418237","canonicalUrl":"https://aoctrl.com/abb/3AXD50000418237","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000418237","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ580-01-276A-2+B056, LV AC wall-mounted drive for water and wastewater, 75 kW / 276 A at 230 V, IP55, NEMA Type12, frame R8.","salesMarkdown":"## Drive selection notes It delivers 75 kW normal-use output at 276 A from a 200–240 V three-phase supply, with heavy-duty capability of 55 kW at 211 A. The IP55 / NEMA Type12 enclosure suits washdown or dusty environments without a separate cabinet. Frame size R8 and wall-mount format mean the drive occupies floor or wall space directly; plan for the physical footprint and 65 dB(A) fan noise at full load. Standby loss of 26 W matters for continuous-running installations where idle power adds up. Communication is limited to CAN — no onboard industrial Ethernet port. If the plant backbone runs PROFINET or EtherNet/IP, a separate gateway or option module is needed. Analog I/O is 2 inputs and 2 outputs; digital I/O counts 6 inputs and 3 outputs. The normal-use output current of 276 A (light-overload 273 A) is the figure to size motor cables and upstream protection. The drive is rated for 110 kV·A apparent power, with a power factor of 0.98 at rated conditions. Maximum ambient temperature is 40 °C. Altitude rating is 4000 m. Efficiency class IE2 is the baseline for this generation. Power consumption at rated load is 3571 W, with standby loss of 26 W.","metaTitle":"3AXD50000418237 ABB ACQ580-01-276A-2+B056 75 kW Drive, 276 A","metaDescription":"ABB ACQ580-01-276A-2+B056 LV AC wall-mounted drive, 75 kW normal use, 276 A output, 230 V input, IP55, NEMA 12, active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"SCIP":"9bc1c3a5-044b-4b84-a7d2-7d41a29f4caa Finland","Altitude":"4000 m","Includes":"Control unit","Frame Size":"R8","Power Factor":"0.98","Sound dB (A)":"65 dB(A)","Standby Loss":"26 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP55","Apparent Power Output":"110 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"3571 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"75 kW","Output Current, Normal Use (In)":"276 A","Output Power, Heavy-Duty Use (PhD)":"55 kW","Output Current, Heavy-Duty Use (IhD)":"211 A","Output Power, Light-Overload Use (PlD)":"75 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"273 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000418237","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000418237/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation is available for this drive?","answer":"RoHS compliance per EU 2011/65/EU (date 20240508), REACH declaration (date 20250905), SCIP number 9bc1c3a5-044b-4b84-a7d2-7d41a29f4caa Finland, and WEEE category 4."},{"question":"What are the key output ratings for normal and heavy duty?","answer":"Normal use: 75 kW, 276 A. Heavy duty: 55 kW, 211 A. Light overload: 75 kW, 273 A. Input is 200–240 V three-phase."},{"question":"What enclosure protection does this drive have?","answer":"IP55 and NEMA Type12, suitable for washdown and dusty environments. Wall-mounted, frame size R8."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000418237","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000418237 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}