{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000429066","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000429066","canonicalUrl":"https://aoctrl.com/abb/3AXD50000429066","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000429066","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880 R8 wall-mounted VFD, 380-480 V 3-phase, 75 kW normal use / 145 A, IP21, NEMA 1, BACnet, includes control unit.","salesMarkdown":"The 3AXD50000429066 is an ABB ACS880 R8 frame drive rated for 75 kW normal use (145 A output) and 55 kW heavy-duty use (106 A) on a 380-480 V three-phase supply. Light-overload use is 138 A at 75 kW, which mirrors the normal-use power but with a slightly lower current ceiling. The drive ships with a control unit included, wall-mounted in an IP21 / NEMA 1 enclosure — suitable for indoor clean environments, not washdown areas. Ambient temperature tops out at 55 °C, and the unit is rated for installation up to 4000 m altitude, with derating expected above 1000 m per standard practice. Efficiency is IE2 class, and the drive is exempt from EU ecodesign energy-efficiency reporting under Regulation EU/2019/1781 §2.3.d because it is a low-harmonic type. Standby loss sits at 72 W; full-load power consumption is 2577 W. Apparent power output is 100 kVA. Onboard I/O includes 2 analog inputs, 2 analog outputs, 6 digital inputs, and 3 digital outputs. No onboard industrial Ethernet port — the drive lists 0 hardware interfaces for Industrial Ethernet, so fieldbus connectivity is via the built-in BACnet port. For PROFINET, EtherNet/IP, or Modbus TCP, an optional fieldbus adapter module is required.","metaTitle":"3AXD50000429066 ACS880 R8 VFD, 75 kW / 145 A, IP21","metaDescription":"3AXD50000429066 ACS880 R8 drive, 75 kW normal use (145 A), 55 kW heavy-duty (106 A). IP21, NEMA 1, BACnet, 380-480 V 3-phase. Current lifecycle stage, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"c41cae70-029d-4bd5-b843-6eabecf29170 Finland","title":"3AXD50000429066","Altitude":"4000 m","Includes":"Control unit","Frame Size":"R8","description":"LV AC ultra-low harmonic wall-mounted drive for HVAC, IEC: Pn 75 kW, 145 A, 400 V, UL: Pld 100 Hp, 124 A, 480 V (ACH580-31-145A-4)","Power Factor":"1.00","Sound dB (A)":"68 dB(A)","Standby Loss":"72 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 55 °C","Ecodesign Exemption":"Energy efficiency data is not provided for the drive. The low-harmonic drives are exempt from the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.d).","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP21","Apparent Power Output":"100 kV·A","Communication Protocol":"BACNET","Power Consumption (@Pcons)":"2577 W","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"75 kW","Output Current, Normal Use (In)":"145 A","Output Power, Heavy-Duty Use (PhD)":"55 kW","Output Current, Heavy-Duty Use (IhD)":"106 A","Output Power, Light-Overload Use (PlD)":"75 kW","Certificates and Declarations/RoHS Date":"20240508","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"138 A","Technical UL/Output Power, Normal Use (UL)":"100 Hp","Technical UL/Output Current, Normal Use (UL)":"124 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"75 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"96 A","Technical UL/Output Power, Light-Overload Use (UL)":"100 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"124 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/085f93ea2b8fc43f9c61e70fdb087634.pdf","sourceUrl":"https://www.abb.com/global/en/products/3axd50000429066"},"ai":{"faq":[{"question":"What is the closest alternative to this drive in the same family?","answer":"Within the ACS880 family, the closest peer is a different frame size or voltage variant. This R8 frame at 75 kW / 145 A is the normal-use rating; a heavy-duty-only application might use a higher-frame drive with a lower continuous rating. No pin-compatible direct drop-in exists — frame size and power stage differ."},{"question":"What is the SCIP number for this drive?","answer":"The SCIP number is c41cae70-029d-4bd5-b843-6eabecf29170 (Finland)."},{"question":"What compliance documentation is available?","answer":"RoHS (Directive 2011/65/EU, compliance date 20240508), REACH (contains >0.1% substances, date 20250905), SCIP number c41cae70-029d-4bd5-b843-6eabecf29170, WEEE category 4, and UL listings for normal use (100 Hp, 124 A) and heavy-duty use (75 Hp, 96 A)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000429066","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000429066 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}