{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000462773","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000462773","canonicalUrl":"https://aoctrl.com/abb/3AXD50000462773","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000462773","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS580, LV AC Packaged Drive with Disconnect Means, Frame R1, 3-phase, 380...500 V, IP21, NEMA Type 1, UL Light-Overload 3 A / 1.5 Hp at 480 V.","salesMarkdown":"It runs on 3-phase 380...500 V input at 50/60 Hz and is rated for UL light-overload use at 3 A / 1.5 Hp (480 V) or heavy-duty at 2.1 A / 1 Hp. The enclosure is IP21 with a NEMA Type 1 rating, suited for indoor panel mounting where drips and falling dirt are the main concerns. The UL light-overload rating (3 A, 1.5 Hp) is the one to size against for typical variable-torque loads like fans and pumps — it gives you headroom over the heavy-duty figure (2.1 A, 1 Hp), which applies to constant-torque or high-starting-duty applications. The 380...500 V input range covers common 400 V and 480 V three-phase networks without a transformer. Frame R1 is the smallest mechanical package in the ACS580 family; check gland-plate space and DIN-rail or backplate mounting provisions before panel layout. ## Integration Notes The built-in disconnect means simplifies panel wiring — no separate disconnect switch required upstream for the drive branch circuit. IP21 and NEMA Type 1 mean it's clean enough for a ventilated electrical room but not for washdown areas.","metaTitle":"ABB 3AXD50000462773 ACS580 Drive, R1, 3 A, 480 V","metaDescription":"ABB 3AXD50000462773 ACS580 LV AC packaged drive, frame R1, 3-phase 380-500 V, UL light-overload 3 A / 1.5 Hp at 480 V. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R1","Frequency (f)":"50/60 Hz","lifecycle_stage":"current","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 500 V","Degree of Protection":"IP21","Technical UL/Output Power, Heavy-Duty Use (UL)":"1 Hp","Technical UL/Output Current, Heavy-Duty Use (UL)":"2.1 A","Technical UL/Output Power, Light-Overload Use (UL)":"1.5 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"3 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000462773","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000462773/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive?","answer":"Frame size R1, the smallest in the ACS580 family."},{"question":"What input voltage and frequency does it accept?","answer":"3-phase 380...500 V, 50/60 Hz."},{"question":"What enclosure protection does it have?","answer":"IP21 (drip-proof) and NEMA Type 1 (indoor, falling dirt)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000462773","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000462773 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}