{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000662487","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000662487","canonicalUrl":"https://aoctrl.com/abb/3AXD50000662487","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000662487","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS180-04N-07A2-4 LV AC machinery drive module, 3 kW / 7.2 A normal use, 380-480 V 3-phase, frame R1, IP20, IE2.","salesMarkdown":"## Drive module for 3 kW machinery The ABB 3AXD50000662487 is an ACS180-04N-07A2-4 LV AC machinery drive module rated for 3 kW normal-use output at 7.2 A, with heavy-duty capability down to 2.2 kW at 5.6 A. It runs on 380-480 V three-phase input and covers 47.5 to 63 Hz. Frame size R1 keeps it compact for panel mounting, and the IP20 enclosure suits clean indoor environments. The 3 kW normal-use rating at 7.2 A drives a standard 4-pole induction motor on 400 VAC. Heavy-duty use at 2.2 kW / 5.6 A handles constant-torque loads like conveyors or mixers. Light-overload use at 6.8 A keeps the same 3 kW output for variable-torque fans and pumps. Standby loss of 9 W means the drive pulls under 10 W when the motor is stopped — relevant for energy-conscious panel designs. Ambient temperature max of 40 °C sets the derating baseline; above that, output current must be reduced. The IE2 efficiency level meets basic energy regulations for most industrial applications. Open-type NEMA enclosure means it relies on the panel's own cooling — no external fan required, but keep ventilation clear.","metaTitle":"ABB 3AXD50000662487 ACS180 drive module, 3 kW, 7.2 A","metaDescription":"ABB ACS180-04N-07A2-4 LV AC machinery drive module. 3 kW normal use, 7.2 A output, 380-480 V 3-phase input. IP20, frame R1, IE2. Active production. SCIP registered.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"5d07f008-496e-4abd-8f50-616cb485c791 Finland","Frame Size":"R1","Standby Loss":"9 W","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Apparent Power Output":"5.0 kV·A","Output Power, Normal Use (Pn)":"3 kW","Output Current, Normal Use (In)":"7.2 A","Output Power, Heavy-Duty Use (PhD)":"2.2 kW","Output Current, Heavy-Duty Use (IhD)":"5.6 A","Output Power, Light-Overload Use (PlD)":"3 kW","Output Current, Light-Overload Use (IlD)":"6.8 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000662487","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000662487/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive?","answer":"Frame size R1 — a compact footprint for DIN-rail or backplate mounting in control panels."},{"question":"What compliance documentation is available?","answer":"The drive is SCIP registered (5d07f008-496e-4abd-8f50-616cb485c791 Finland) and classified under WEEE Category 5. Standard ABB declarations for RoHS, REACH, and CE are provided with the unit."},{"question":"What are the key electrical ratings?","answer":"Normal use: 3 kW, 7.2 A. Heavy-duty use: 2.2 kW, 5.6 A. Light-overload use: 3 kW, 6.8 A. Input: 380-480 V 3-phase, 47.5-63 Hz."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000662487","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000662487 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}