{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000707232","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000707232","canonicalUrl":"https://aoctrl.com/abb/3AXD50000707232","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000707232","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ80 series, LV AC drive module for solar pump, 0.75 kW normal use, 2.6 A, 380-480 V 3-phase, frame size R0, IP20, CAN interface.","salesMarkdown":"The 3AXD50000707232: The normal-use output (Pn 0.75 kW, In 2.6 A) is the rating for continuous solar pump duty. For heavier transient loads — say, a pump starting against a closed valve — the heavy-duty rating drops to 0.55 kW at 1.8 A. Light-overload use is rated 0.75 kW at 2.5 A, essentially matching normal use. The 380–480 V input range covers standard three-phase mains across most regions. Standby loss is 15 W, and full power consumption hits 44 W — useful numbers for panel thermal budgeting. The drive carries 6 digital inputs and 3 digital outputs, plus 2 analog inputs and 2 analog outputs — enough for basic pump control (start/stop, speed reference, feedback) without an external PLC. Communication is via CAN; there is no industrial Ethernet interface (0 hardware interfaces for Ethernet). For systems needing Modbus TCP or PROFINET, plan on a separate gateway or a different drive variant. ## Mechanical and environmental Frame size R0 keeps the footprint compact. IP20 protection means it is suited for clean indoor panel mounting; NEMA Open Type confirms no additional enclosure rating. Maximum ambient temperature is 50 °C, and operating humidity spans 5–95 % RH. The drive includes a CR2032 lithium coin cell (220 mAh, 3 V) for backup — note the battery for spares planning. Acoustic noise is 63.1 dB(A), typical for a drive of this size.","metaTitle":"ABB 3AXD50000707232 ACQ80 Solar Pump Drive, 0.75 kW, 2.6 A","metaDescription":"ABB ACQ80-04-0kW75-4 LV AC drive module for solar pump. Active, 0.75 kW normal use, 2.6 A, 380-480 V 3-phase. Frame R0, IP20, CAN. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"97657ee2-2ad1-409a-811f-7a3734b200a6 Finland","Includes":"Control unit","Frame Size":"R0","Sound dB (A)":"63.10 dB(A)","Standby Loss":"15 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 50 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Apparent Power Output":"2.0 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"44 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"0.75 kW","Output Current, Normal Use (In)":"2.6 A","Output Power, Heavy-Duty Use (PhD)":"0.55 kW","Output Current, Heavy-Duty Use (IhD)":"1.8 A","Output Power, Light-Overload Use (PlD)":"0.75 kW","Certificates and Declarations/RoHS Date":"20240603","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"2.5 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000707232","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000707232/alternatives.json"},"ai":{"faq":[{"question":"What are the key output ratings for this drive?","answer":"Normal-use output is 0.75 kW at 2.6 A. Heavy-duty use is 0.55 kW at 1.8 A. Light-overload use is 0.75 kW at 2.5 A. Input is 380–480 V three-phase."},{"question":"What compliance documentation is available for this drive?","answer":"RoHS compliance follows EU Directive 2011/65/EU (date 20240603). REACH declaration confirms substances >0.1% (date 20250905). SCIP number is 97657ee2-2ad1-409a-811f-7a3734b200a6 Finland."},{"question":"Does the drive include a control unit?","answer":"Yes, the module includes the control unit, so it is a complete drive ready for integration."},{"question":"What communication protocols does it support?","answer":"It supports CAN communication. There are no industrial Ethernet interfaces."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000707232","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000707232 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}