{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000707447","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000707447","canonicalUrl":"https://aoctrl.com/abb/3AXD50000707447","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000707447","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ80-04-18kW5-4 LV AC drive module for solar pump, IEC: Pn 18.5 kW, 38 A, 400 V, IP20, R3 frame.","salesMarkdown":"## Drive module for solar pump duty It delivers 18.5 kW normal-use output at 38 A, with a heavy-duty rating of 15 kW at 32 A for sustained overload scenarios. Input accepts 380–480 V three-phase, 47.5–63 Hz, and the module is rated IP20 for panel-mount installation in an R3 frame. ## Output ratings and duty cycles Three duty ratings are defined: light-overload (18.5 kW, 36 A), normal-use (18.5 kW, 38 A), and heavy-duty (15 kW, 32 A). Apparent power output is 26 kV·A, matching the normal-use current at 400 V. ## Power and thermal profile Power consumption at full load is 497 W, with standby loss at 37 W — relevant for off-grid solar arrays where idle draw drains batteries. Maximum ambient temperature is 50 °C; operating humidity 5–95 % non-condensing. Sound level 58.8 dB(A) at rated load. The R3 frame includes a control unit and a lithium coin cell (CR2032, 220 mAh) for real-time clock backup. ## Control and I/O Integrated I/O: 2 analog inputs, 2 analog outputs, 6 digital inputs, 3 digital outputs. Communication is via CAN bus — no onboard Ethernet (0 Industrial Ethernet interfaces). For Modbus TCP or PROFINET, a separate fieldbus adapter is required. Efficiency class is IE2.","metaTitle":"ABB 3AXD50000707447 ACQ80 solar pump drive, 18.5 kW, 38 A","metaDescription":"ABB ACQ80-04-18kW5-4 LV AC drive module for solar pumps. 18.5 kW normal use, 38 A output, IP20, R3 frame. Active production. RFQ for lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"2833fe5f-6cc6-4962-a94c-7cc7cd36b801 Finland","Includes":"Control unit","Frame Size":"R3","Sound dB (A)":"58.8 dB(A)","Standby Loss":"37 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 50 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Apparent Power Output":"26 kV·A","Communication Protocol":"CAN","Power Consumption (@Pcons)":"497 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, CR2032, 220 mAh, 3 V, 1 pc, 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"18.5 kW","Output Current, Normal Use (In)":"38 A","Output Power, Heavy-Duty Use (PhD)":"15 kW","Output Current, Heavy-Duty Use (IhD)":"32 A","Output Power, Light-Overload Use (PlD)":"18.5 kW","Certificates and Declarations/RoHS Date":"20240603","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"36 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000707447","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000707447/alternatives.json"},"ai":{"faq":[{"question":"What does the heavy-duty output rating mean for sizing?","answer":"The heavy-duty rating (15 kW, 32 A) is the continuous output under overload conditions — use this for pump starting torque or variable solar input. The normal-use rating (18.5 kW, 38 A) applies to steady-state, non-overload operation."},{"question":"What communication protocols does the drive support?","answer":"The onboard interface is CAN bus only. There are zero Industrial Ethernet ports, so protocols like Modbus TCP, PROFINET, or EtherNet/IP require an optional fieldbus adapter."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000707447","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000707447 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}