{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000716555","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000716555","canonicalUrl":"https://aoctrl.com/abb/3AXD50000716555","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000716555","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS180 series, LV AC machinery drive module, 3AXD50000716555, 4 kW / 9.4 A normal use, 380-480 V 3-phase, IP20, MODBUS.","salesMarkdown":"The ABB 3AXD50000716555 is an ACS180-04N-09A4-4 LV AC machinery drive module in frame size R1, rated for 4 kW normal use at 9.4 A and 3 kW heavy-duty use at 7.2 A on a 380-480 V 3-phase supply. The heavy-duty current is the one that governs continuous motor load in a constant-torque application — size the branch circuit for that, not the normal-use figure. Input frequency range is 47-63 Hz, so it handles 50 or 60 Hz line without derating. IP20 enclosure, open type per NEMA, rated for maximum 40 °C ambient and 2000 m altitude. Mounts as a module — DIN rail or panel mount, frame R1 footprint. Operating humidity 5-95% non-condensing. Standby loss is 9 W, so no forced cooling needed in a ventilated cabinet; sound level 50.9 dB(A) is quiet enough for a machine-side install. Built-in MODBUS RTU on the RS-485 port — no option card required. Two analog inputs, one analog output, four digital inputs, two digital outputs. That covers a basic speed reference and run/stop set; for additional fieldbus (PROFINET, EtherNet/IP) you need the optional module slot, which is empty on this variant (0 industrial Ethernet interfaces).","metaTitle":"ABB 3AXD50000716555 ACS180 drive, 4 kW, 9.4 A, 400 V","metaDescription":"ABB ACS180-04N-09A4-4 LV AC drive, 4 kW normal use, 9.4 A, 380-480 V, IP20, MODBUS, active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"5d07f008-496e-4abd-8f50-616cb485c791 Finland","Altitude":"2000 m","Includes":"Control unit","Frame Size":"R1","Power Factor":"0.98","Sound dB (A)":"50.9 dB(A)","Standby Loss":"9 W","Analog Inputs":"2","Frequency (f)":"47 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"1","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Apparent Power Output":"6.5 kV·A","Communication Protocol":"MODBUS","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"No battery / cell included","Number of Digital In/Outputs":"4 / 2","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"4 kW","Output Current, Normal Use (In)":"9.4 A","Output Power, Heavy-Duty Use (PhD)":"3 kW","Output Current, Heavy-Duty Use (IhD)":"7.2 A","Output Power, Light-Overload Use (PlD)":"4 kW","Certificates and Declarations/RoHS Date":"20250106","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"8.9 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"3 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"6.3 A","Technical UL/Output Power, Light-Overload Use (UL)":"5 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"7.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000716555","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000716555/alternatives.json"},"ai":{"faq":[{"question":"What are the key output ratings for this drive?","answer":"Normal use: 4 kW, 9.4 A. Heavy-duty use: 3 kW, 7.2 A. Light-overload use: 4 kW, 8.9 A. UL ratings: 5 Hp light-overload at 7.6 A, 3 Hp heavy-duty at 6.3 A."},{"question":"What compliance documentation is available?","answer":"RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863 (declaration date 20250106). REACH declaration (date 20250905) indicates substances above 0.1% mass percentage. SCIP number 5d07f008-496e-4abd-8f50-616cb485c791 Finland."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000716555","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000716555 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}