{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000747511","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000747511","canonicalUrl":"https://aoctrl.com/abb/3AXD50000747511","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000747511","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS530-01-03A4-4, 1.1 kW, 3.3 A, 380-480 V 3-phase, IP20, frame R1.","salesMarkdown":"The ABB 3AXD50000747511 is an ACS530-01-03A4-4 drive rated for 1.1 kW normal-use output at 3.3 A, fed from a 380 to 480 V three-phase supply. Standby loss sits at 14 W, a figure worth noting when sizing the cabinet cooling or calculating total heat load on a sealed enclosure. The 1.1 kW normal-use rating (Pn) and 3.3 A output current (In) define the continuous motor capacity on a standard 400 V supply. Light-overload duty (PlD) is also 1.1 kW at 3.1 A, so the drive is sized for constant-torque loads like conveyors or pumps without headroom for short-term overload — if your application demands a 150 % overload for 60 seconds, step up to the next frame. The 2.3 kVA apparent power output confirms the drive's transformer capacity for sizing the upstream line reactor or input fusing. IP20 protection means it is suited for clean, dry indoor panel mounting; no wash-down capability, so keep it out of splash zones. ## Installation notes Mounts as an open-type module (NEMA Open Type) inside a cabinet. The 47.5 to 63 Hz input frequency range covers both 50 Hz and 60 Hz grids without derating. Maximum ambient temperature is 40 °C; above that, derate the output current per the thermal curve in the manual. Efficiency class IE2 is standard for this power band — not premium efficiency, but adequate for most constant-speed applications where the drive is paired with an IE2 motor.","metaTitle":"ABB 3AXD50000747511 ACS530-01-03A4-4, 1.1 kW, 3.3 A","metaDescription":"ABB ACS530-01-03A4-4 drive, 1.1 kW normal-use output, 3.3 A rated current, 380-480 V 3-phase, IP20, frame R1. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R1","Standby Loss":"14 W","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Apparent Power Output":"2.3 kV·A","Output Power, Normal Use (Pn)":"1.1 kW","Output Current, Normal Use (In)":"3.3 A","Output Power, Light-Overload Use (PlD)":"1.1 kW","Output Current, Light-Overload Use (IlD)":"3.1 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000747511","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000747511/alternatives.json"},"ai":{"faq":[{"question":"What is the standby loss of this drive?","answer":"Standby loss is 14 W, a figure to include in enclosure heat-load calculations."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000747511","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000747511 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}