{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000761067","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000761067","canonicalUrl":"https://aoctrl.com/abb/3AXD50000761067","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000761067","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ580-01 wall-mounted drive, 3-phase 208-240 V, UL Pld 2 Hp / 7.5 A light-overload, IP55, NEMA Type12, 50/60 Hz.","salesMarkdown":"The 3AXD50000761067: The enclosure is IP55 with a NEMA Type12 rating, so it handles hose-down and dust in pump rooms or treatment-plant walls without an extra cabinet. The light-overload figure (7.5 A, 2 Hp) gives headroom for variable-torque centrifugal pumps that rarely pull full current. Match your motor nameplate to the heavy-duty column unless the pump curve is squarely variable-torque. Input voltage is 208... 240 V three-phase — common in North American light-industrial panels. The 50/60 Hz rating means it ships for either grid frequency; no configuration change needed at the terminals.","metaTitle":"ABB 3AXD50000761067 ACQ580-01 drive, 2 Hp, 7.5 A, 208-240 V","metaDescription":"ABB ACQ580-01 wall-mounted drive for water/wastewater. 3-phase 208-240 V input, IP55, NEMA 12. UL heavy-duty 1.5 A / light-overload 7.5 A. Active production. Source via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"Frame Size":"Undefined","Frequency (f)":"50/60 Hz","lifecycle_stage":"current","Number of Phases":"3-phase","Enclosure Type NEMA":"Type12","Input Voltage (Uin)":"208 ... 240 V","Degree of Protection":"IP55","Technical UL/Output Power, Heavy-Duty Use (UL)":"1.5 Hp","Technical UL/Output Current, Heavy-Duty Use (UL)":"1.5 A","Technical UL/Output Power, Light-Overload Use (UL)":"2 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"7.5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000761067","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000761067/alternatives.json"},"ai":{"faq":[{"question":"What are the key UL ratings for this drive?","answer":"Heavy-duty use: 1.5 Hp, 1.5 A. Light-overload use: 2 Hp, 7.5 A. Both are UL-listed."},{"question":"What enclosure protection does it have?","answer":"IP55 and NEMA Type12, suitable for washdown and dusty environments."},{"question":"What input voltage and frequency does it accept?","answer":"3-phase 208... 240 V at 50/60 Hz."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000761067","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000761067 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}