{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000798926","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000798926","canonicalUrl":"https://aoctrl.com/abb/3AXD50000798926","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000798926","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS580-01 general purpose wall-mounted drive, 3AXD50000798926, Frame R9, 208-240 V, 3-phase, 343 A light-overload (123 Hp), 273 A heavy-duty (100 Hp), NEMA 1, IP21.","salesMarkdown":"Wall-mounted drive, order code 3AXD50000798926, sized for 208-240 V three-phase input. Frame R9, NEMA 1 enclosure with IP21 protection — indoor wall-mount, no extra cabinet required for basic environments. Rated 343 A light-overload (123 Hp) and 273 A heavy-duty (100 Hp) per UL. Heavy-duty figure governs continuous motor load; light-overload covers applications with occasional peak demand. Both ratings at 240 V. Light-overload rating of 343 A at 123 Hp covers variable-torque fans and centrifugal pumps where peak current is short-duration. Pick the duty class that matches your motor nameplate and load profile — the drive handles both, but the continuous rating must not be exceeded. NEMA 1 enclosure with IP21 protection — drip-proof, indoor use. Frame R9 determines mounting hole pattern and clearance; verify panel depth for heat sink projection. Wall-mount only; no floor-standing kit needed for this frame. UL-listed per the heavy-duty and light-overload output ratings. RoHS and CE compliance typical for the series; request the declaration of conformity with your RFQ if required for your site's compliance file.","metaTitle":"ABB 3AXD50000798926 ACS580-01 VFD, 343 A, 123 Hp","metaDescription":"ABB ACS580-01 wall-mounted drive, 208-240 V, 3-phase, 343 A light-overload (123 Hp), 273 A heavy-duty (100 Hp). Frame R9, NEMA 1, IP21. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"Frame Size":"R9","Frequency (f)":"50/60 Hz","lifecycle_stage":"current","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"208 ... 240 V","Degree of Protection":"IP21","Technical UL/Output Power, Heavy-Duty Use (UL)":"100 Hp","Technical UL/Output Current, Heavy-Duty Use (UL)":"273 A","Technical UL/Output Power, Light-Overload Use (UL)":"123 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"343 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000798926","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000798926/alternatives.json"},"ai":{"faq":[{"question":"What enclosure and protection rating does it have?","answer":"NEMA 1 enclosure with IP21 protection, suitable for indoor wall-mount in dry, drip-free environments."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000798926","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000798926 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}