{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000827626","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000827626","canonicalUrl":"https://aoctrl.com/abb/3AXD50000827626","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000827626","rawCanonicalId":null},"summary":{"shortDescription":"ABB drive, Frame R1, 3-phase input 200...240 V, normal-use output 2.2 kW / 9.8 A, heavy-duty 1.5 kW / 7.4 A, MODBUS, IP20.","salesMarkdown":"The ABB 3AXD50000827626 is a variable-speed drive in Frame Size R1, built for 3-phase 200...240 V input. Normal-use output is rated 2.2 kW / 9.8 A; when the load cycle calls for heavy-duty use, it handles 1.5 kW / 7.4 A. Light-overload use matches the normal-use power at 2.2 kW / 9.3 A. Communication is MODBUS, and the enclosure carries IP20 protection — panel-mount only, no washdown. ## Where the ratings matter Normal-use (2.2 kW / 9.8 A) suits variable-torque loads such as centrifugal fans or pumps where peak demand is intermittent. Power factor sits at 0.98, and standby loss is 7 W — low enough that leaving it powered for bus communication won't sting the electric bill. Frame R1 keeps the footprint compact for a 2.2 kW drive — fits a standard panel backplate without crowding. The drive includes a control unit, so no separate order for that. Altitude rating is 2000 m; above that, derate per the datasheet. Ambient temperature max is 40 °C, humidity range 5...95% non-condensing.","metaTitle":"ABB 3AXD50000827626 Drive, 2.2 kW / 9.8 A, Frame R1","metaDescription":"ABB drive 3AXD50000827626, 2.2 kW normal use (9.8 A), 1.5 kW heavy-duty (7.4 A). 200-240 V 3-phase, MODBUS, IP20, Frame R1. Active production — source to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"SCIP":"a8a72b30-d5e5-4de6-b0f8-01a627cfc18e Finland","Altitude":"2000 m","Includes":"Control unit","Frame Size":"R1","Power Factor":"0.98","Sound dB (A)":"51.8 dB(A)","Standby Loss":"7 W","Analog Inputs":"2","Frequency (f)":"47 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"1","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP20","Apparent Power Output":"3.9 kV·A","Communication Protocol":"MODBUS","Power Consumption (@Pcons)":"76 W","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"No battery / cell included","Number of Digital In/Outputs":"4 / 2","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"2.2 kW","Output Current, Normal Use (In)":"9.8 A","Output Power, Heavy-Duty Use (PhD)":"1.5 kW","Output Current, Heavy-Duty Use (IhD)":"7.4 A","Output Power, Light-Overload Use (PlD)":"2.2 kW","Certificates and Declarations/RoHS Date":"20250106","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"9.3 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"2 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"7.5 A","Technical UL/Output Power, Light-Overload Use (UL)":"2 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"9.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000827626","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000827626/alternatives.json"},"ai":{"faq":[{"question":"What are the key output ratings for this drive?","answer":"Normal-use output is 2.2 kW / 9.8 A. Heavy-duty use is 1.5 kW / 7.4 A. Light-overload use is 2.2 kW / 9.3 A. UL ratings are 2 Hp / 7.5 A (heavy-duty) and 2 Hp / 9.6 A (light-overload)."},{"question":"What is the input voltage and phase requirement?","answer":"Three-phase input, 200...240 V, 47...63 Hz."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000827626","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000827626 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}