{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000874170","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000874170","canonicalUrl":"https://aoctrl.com/abb/3AXD50000874170","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000874170","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS180 series LV AC machinery drive module, 3AXD50000874170, IEC: Pn 15 kW, 32.0 A, 400 V, UL: Pld 20 Hp, 27.0 A, 460 V, Frame Size R3, IP20, Modbus.","salesMarkdown":"The 3AXD50000874170: The drive includes a control unit, 2 analog inputs and 1 analog output, plus 4 digital inputs and 2 digital outputs. Communication is Modbus (no onboard industrial Ethernet). Standby loss is 23 W; sound level is 66 dB(A). Rated for installation up to 2000 m altitude, 5…95 % RH, and a maximum ambient of 40 °C. Efficiency class IE2, power factor 0.98. The three overload classes let you match the drive to the load profile. Normal-use (Pn 15 kW, In 32.0 A) covers constant-torque applications at rated current. Light-overload (PlD 15 kW, IlD 30.5 A) gives extra headroom for occasional peak loads. Heavy-duty (PhD 11 kW, IhD 25.0 A) is the conservative rating for high-starting-torque or cyclic loads — use this one if the motor duty cycle is demanding or ambient is near the 40 °C limit. Frame R3 and IP20 open-type mean it mounts in a clean, dry cabinet — not outdoors or in washdown areas. The Modbus interface is fixed; no fieldbus option slot for PROFINET or EtherNet/IP. If the line requires Ethernet-based control, this isn't the variant.","metaTitle":"ABB 3AXD50000874170 ACS180 Drive Module, 15 kW, 32.0 A, Fram","metaDescription":"ABB ACS180-04N-033A-4 machinery drive module, 15 kW normal-use, 32.0 A output, 380-480 V 3-phase input, Frame R3, IP20, Modbus, current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"ce087935-c5d0-48c8-89ae-769efc3dfb30 Finland","Altitude":"2000 m","Includes":"Control unit","Frame Size":"R3","Power Factor":"0.98","Sound dB (A)":"66 dB(A)","Standby Loss":"23 W","Analog Inputs":"2","Frequency (f)":"47 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"1","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Apparent Power Output":"22 kV·A","Communication Protocol":"MODBUS","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"No battery / cell included","Number of Digital In/Outputs":"4 / 2","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"15 kW","Output Current, Normal Use (In)":"32.0 A","Output Power, Heavy-Duty Use (PhD)":"11 kW","Output Current, Heavy-Duty Use (IhD)":"25.0 A","Output Power, Light-Overload Use (PlD)":"15 kW","Certificates and Declarations/RoHS Date":"20250106","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"30.5 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"15 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"21.0 A","Technical UL/Output Power, Light-Overload Use (UL)":"20 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"27.0 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000874170","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000874170/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation is available for this drive?","answer":"RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863 (RoHS date 20250106). REACH: contains substances above 0.1 mass percentage (REACH date 20250905). SCIP number ce087935-c5d0-48c8-89ae-769efc3dfb30 Finland is on file."},{"question":"What are the key output ratings for this drive?","answer":"IEC: normal-use 15 kW / 32.0 A, heavy-duty 11 kW / 25.0 A, light-overload 15 kW / 30.5 A. UL: light-overload 20 Hp / 27.0 A, heavy-duty 15 Hp / 21.0 A."},{"question":"What is the SCIP number for this product?","answer":"SCIP number ce087935-c5d0-48c8-89ae-769efc3dfb30 Finland."},{"question":"What is the altitude rating of this drive?","answer":"Rated for installation up to 2000 m altitude."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000874170","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000874170 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}