{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000956647","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000956647","canonicalUrl":"https://aoctrl.com/abb/3AXD50000956647","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000956647","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH180-04S-06A9-1, LV AC micro drive module for HVAC, IEC: Pn 1.1 kW, 6.9 A, 230 V, UL: Pld 1.5 Hp, 6.6 A, 230 V, frame R1, IP20, BACnet.","salesMarkdown":"The 3AXD50000956647: Normal-use output (Pn 1.1 kW, In 6.9 A) is the continuous rating for typical fan and pump curves. Heavy-duty use (PhD 0.75 kW, IhD 4.5 A) applies when the load demands higher peak torque or a constant-torque profile — a positive-displacement pump or a small conveyor, for example. Light-overload use (PlD 1.1 kW, IlD 6.6 A) sits between the two; the 6.6 A figure is slightly below the normal-use 6.9 A, so for a straight fan load the normal-use number is the one to size against. ## Fieldbus and I/O BACnet is the onboard protocol — no option card needed. That makes this drive a direct fit for building-automation networks where the BMS talks BACnet MS/TP or BACnet/IP. Two analog inputs and one analog output handle duct static-pressure transducers or valve feedback; the 4 digital inputs and 2 digital outputs cover start/stop, fault reset, and run-status handshakes. No industrial Ethernet interface on this variant (0 hardware interfaces for Industrial Ethernet), so if the plant standard is PROFINET or EtherNet/IP, this isn't the drop. The drive communicates over BACnet only.","metaTitle":"ABB 3AXD50000956647 ACH180 Micro Drive, 1.1 kW, 6.9 A, 230 V","metaDescription":"ABB ACH180 micro drive, 1.1 kW / 6.9 A normal use, 230 V 1-phase, IP20, BACnet, frame R1. Current production. RoHS/REACH dated. Source to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"SCIP":"030cdeeb-e61c-40db-b392-d77adebb2036 Finland","Altitude":"2000 m","Includes":"Control unit","Frame Size":"R1","Power Factor":"0.98","Sound dB (A)":"51.80 dB(A)","Standby Loss":"- W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"1","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"1-phase","Temperature Rating":"Maximum 60 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP20","Apparent Power Output":"2.7 kV·A","Communication Protocol":"BACNET","Number of Digital In/Outputs":"4 / 2","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"1.1 kW","Output Current, Normal Use (In)":"6.9 A","Output Power, Heavy-Duty Use (PhD)":"0.75 kW","Output Current, Heavy-Duty Use (IhD)":"4.5 A","Output Power, Light-Overload Use (PlD)":"1.1 kW","Certificates and Declarations/RoHS Date":"20240110","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"6.6 A","Technical UL/Output Power, Normal Use (UL)":"1.5 Hp","Technical UL/Output Current, Normal Use (UL)":"6.9 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"1.0 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"4.5 A","Technical UL/Output Power, Light-Overload Use (UL)":"1.5 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"6.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000956647","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000956647/alternatives.json"},"ai":{"faq":[{"question":"What is the SCIP number for this drive?","answer":"SCIP number 030cdeeb-e61c-40db-b392-d77adebb2036 Finland is listed for EU waste reporting."},{"question":"What is the maximum operating altitude?","answer":"Rated for 2000 m altitude without derating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000956647","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000956647 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}