{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000956654","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000956654","canonicalUrl":"https://aoctrl.com/abb/3AXD50000956654","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000956654","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH180 series, LV AC micro drive module for HVAC, IEC: Pn 1.5 kW, 7.8 A, 230 V, UL: Pld 2.0 Hp, 7.5 A, 230 V (ACH180-04S-07A8-1).","salesMarkdown":"## Ratings and duty cycles The 3AXD50000956654: Three duty ratings are defined: normal-use (Pn 1.5 kW / In 7.8 A), heavy-duty (PhD 1.1 kW / IhD 6.6 A), and light-overload (PlD 1.5 kW / IlD 7.5 A). The heavy-duty figure governs continuous motor load in high-torque applications; the light-overload figure matches normal-use power with slightly lower current, suggesting a different thermal model for fan/pump profiles. UL current ratings mirror the IEC values: 7.8 A normal-use, 6.6 A heavy-duty, 7.5 A light-overload. Power factor is 0.98; apparent power output is 3.1 kV·A. Built-in BACnet protocol — no option card needed for BAS integration. Two analog inputs, one analog output. Four digital inputs, two digital outputs. No industrial Ethernet interface on this variant; communication is via serial BACnet MS/TP or similar. Rated for 2000 m altitude, 60 °C maximum ambient. Frequency range 47.5…63 Hz covers 50/60 Hz grids. Sound pressure 51.8 dB(A). Standby loss is listed as — W (not specified).","metaTitle":"ABB 3AXD50000956654 ACH180 Micro Drive, 1.5 kW, 7.8 A","metaDescription":"ABB ACH180 micro drive, 1.5 kW / 2.0 Hp, 7.8 A, 230 V 1-phase. BACnet, IP20, frame R1. Active production. RoHS/REACH compliant. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"SCIP":"030cdeeb-e61c-40db-b392-d77adebb2036 Finland","Altitude":"2000 m","Includes":"Control unit","Frame Size":"R1","Power Factor":"0.98","Sound dB (A)":"51.80 dB(A)","Standby Loss":"- W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"1","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"1-phase","Temperature Rating":"Maximum 60 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP20","Apparent Power Output":"3.1 kV·A","Communication Protocol":"BACNET","Number of Digital In/Outputs":"4 / 2","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"1.5 kW","Output Current, Normal Use (In)":"7.8 A","Output Power, Heavy-Duty Use (PhD)":"1.1 kW","Output Current, Heavy-Duty Use (IhD)":"6.6 A","Output Power, Light-Overload Use (PlD)":"1.5 kW","Certificates and Declarations/RoHS Date":"20240110","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"7.5 A","Technical UL/Output Power, Normal Use (UL)":"2.0 Hp","Technical UL/Output Current, Normal Use (UL)":"7.8 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"1.5 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"6.6 A","Technical UL/Output Power, Light-Overload Use (UL)":"2.0 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"7.5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000956654","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000956654/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does this drive carry?","answer":"RoHS compliant per EU Directive 2011/65/EU (amended 2015/863), REACH declaration with substances above 0.1 mass percentage, and SCIP number 030cdeeb-e61c-40db-b392-d77adebb2036 (Finland). UL listing covers the output ratings."},{"question":"What is the altitude rating?","answer":"2000 m maximum operating altitude."},{"question":"What communication protocol does it use?","answer":"BACnet. No industrial Ethernet interface on this variant."},{"question":"What are the normal-use and heavy-duty output ratings?","answer":"Normal-use: 1.5 kW / 7.8 A (IEC), 2.0 Hp / 7.8 A (UL). Heavy-duty: 1.1 kW / 6.6 A (IEC), 1.5 Hp / 6.6 A (UL). Input is single-phase 200…240 V."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000956654","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000956654 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}