{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000956661","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000956661","canonicalUrl":"https://aoctrl.com/abb/3AXD50000956661","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000956661","rawCanonicalId":null},"summary":{"shortDescription":"ABB, ACH180 series, LV AC micro drive module for HVAC, IEC: Pn 2.2 kW, 9.8 A, 230 V, UL: Pld 3.0 Hp, 9.8 A, 230 V (ACH180-04S-09A8-1).","salesMarkdown":"It is a single-phase 200 to 240 V input, 2.2 kW normal-use output at 9.8 A (IEC), or 3.0 Hp under UL. Frame size R1, IP20 open type, IE2 efficiency, control unit included. The normal-use current of 9.8 A covers constant-torque loads like fans and pumps in HVAC — that's the headline number for sizing. Heavy-duty use drops to 7.5 A (1.5 kW), which is the rating you'd apply for tougher cyclic loads or if you need headroom for short-duration overload. Light-overload use also sits at 9.8 A, effectively matching normal use for most applications. The 0.98 power factor is typical for a modern drive with active rectification; it means the line draw is clean, which helps with panel transformer sizing and harmonic compliance. ## Integration notes Communication is fixed to BACnet — no fieldbus module to swap, so if your BMS speaks BACnet MS/TP or BACnet/IP, this drive drops right in. It carries 2 analog inputs, 1 analog output, and 4 digital I/O (2 outputs). Mounting is module-style, likely on a DIN rail or backplate; the R1 frame is compact for a 2.2 kW drive. Operating temperature maxes at 60 °C, altitude to 2000 m without derating. The 51.8 dB(A) noise level is moderate — fine for a mechanical room, noticeable in an office-adjacent space.","metaTitle":"3AXD50000956661 ABB ACH180-04S-09A8-1 micro drive, 2.2 kW, 9","metaDescription":"ABB ACH180-04S-09A8-1 LV AC micro drive, 2.2 kW normal-use, 9.8 A, 200-240 V, IP20, BACnet, current lifecycle. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"SCIP":"030cdeeb-e61c-40db-b392-d77adebb2036 Finland","Altitude":"2000 m","Includes":"Control unit","Frame Size":"R1","Power Factor":"0.98","Sound dB (A)":"51.80 dB(A)","Standby Loss":"- W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"1","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"1-phase","Temperature Rating":"Maximum 60 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP20","Apparent Power Output":"3.9 kV·A","Communication Protocol":"BACNET","Number of Digital In/Outputs":"4 / 2","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"2.2 kW","Output Current, Normal Use (In)":"9.8 A","Output Power, Heavy-Duty Use (PhD)":"1.5 kW","Output Current, Heavy-Duty Use (IhD)":"7.5 A","Output Power, Light-Overload Use (PlD)":"2.2 kW","Certificates and Declarations/RoHS Date":"20240110","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"9.3 A","Technical UL/Output Power, Normal Use (UL)":"3.0 Hp","Technical UL/Output Current, Normal Use (UL)":"9.8 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"2.0 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"7.5 A","Technical UL/Output Power, Light-Overload Use (UL)":"3.0 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"9.8 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000956661","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000956661/alternatives.json"},"ai":{"faq":[{"question":"What is the SCIP number for this drive?","answer":"The SCIP number is 030cdeeb-e61c-40db-b392-d77adebb2036 Finland."},{"question":"What compliance documentation does this drive carry?","answer":"RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863 (date 20240110); REACH declaration confirms substances above 0.1% mass percentage (date 20250905); UL listing covers output ratings for normal, heavy-duty, and light-overload use."},{"question":"What is the maximum operating altitude?","answer":"The drive is rated for altitudes up to 2000 m without derating."},{"question":"What communication protocol does this drive support?","answer":"BACnet is the fixed protocol — no fieldbus module swap required."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000956661","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000956661 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}