{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000956685","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000956685","canonicalUrl":"https://aoctrl.com/abb/3AXD50000956685","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000956685","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH180 series, LV AC micro drive module, 3AXD50000956685, 1.1 kW / 6.9 A normal duty, 200-240 V 3-phase input, IP20, R1 frame size.","salesMarkdown":"The 3AXD50000956685: Built-in BACnet communication makes it a direct fit for building management system integration without an external gateway. The R1 frame size keeps panel footprint compact, and the IP20 enclosure suits clean indoor cabinet mounting. Normal-use output current of 6.9 A (In) matches a standard 1.1 kW induction motor. Heavy-duty curve drops to 4.6 A (IhD) at 0.75 kW for continuous cyclic loads. Light-overload use holds at 1.1 kW with 6.6 A output for variable-torque fans and pumps. UL ratings: 1.5 Hp normal duty at 6.6 A, 1.0 Hp heavy-duty at 4.6 A. The drive accepts 200-240 V at 47.5-63 Hz. Standby loss is 7 W. Maximum ambient temperature is 60 °C. Altitude rating is 2000 m. ## I/O and control integration The control unit includes 2 analog inputs, 1 analog output, and 4 digital inputs plus 2 digital outputs — enough for basic speed reference, run/stop, and fault feedback without an expansion module. The single BACnet MS/TP port handles the building automation link; there is no second Ethernet port, so daisy-chaining requires an external switch. UL listing covers Open Type enclosure for panel mounting. WEEE category 5 (small equipment) applies for end-of-life take-back in EU markets.","metaTitle":"ABB 3AXD50000956685 ACH180 Micro Drive, 1.1 kW, 6.9 A, 230 V","metaDescription":"ABB ACH180-04S-06A9-2 micro drive, 1.1 kW/6.9 A normal duty, 230 V input, BACnet, IP20, R1 frame. Current production. RoHS/REACH/UL certified. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"SCIP":"a8a72b30-d5e5-4de6-b0f8-01a627cfc18e Finland","Altitude":"2000 m","Includes":"Control unit","Frame Size":"R1","Power Factor":"0.98","Sound dB (A)":"51.80 dB(A)","Standby Loss":"7 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"1","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 60 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP20","Apparent Power Output":"2.7 kV·A","Communication Protocol":"BACNET","Number of Digital In/Outputs":"4 / 2","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"1.1 kW","Output Current, Normal Use (In)":"6.9 A","Output Power, Heavy-Duty Use (PhD)":"0.75 kW","Output Current, Heavy-Duty Use (IhD)":"4.6 A","Output Power, Light-Overload Use (PlD)":"1.1 kW","Certificates and Declarations/RoHS Date":"20240110","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"6.6 A","Technical UL/Output Power, Normal Use (UL)":"1.5 Hp","Technical UL/Output Current, Normal Use (UL)":"6.6 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"1.0 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"4.6 A","Technical UL/Output Power, Light-Overload Use (UL)":"1.5 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"6.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000956685","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000956685/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation is available for this drive?","answer":"RoHS declaration dated 20240110 per EU Directive 2011/65/EU, REACH registration (contains substances >0.1% mass), SCIP number a8a72b30-d5e5-4de6-b0f8-01a627cfc18e Finland, and UL listing for Open Type enclosure."},{"question":"What is the SCIP number for this product?","answer":"The SCIP number is a8a72b30-d5e5-4de6-b0f8-01a627cfc18e Finland, filed for EU waste reporting compliance."},{"question":"What are the key output ratings for motor sizing?","answer":"Normal duty: 1.1 kW at 6.9 A (IEC) or 1.5 Hp at 6.6 A (UL). Heavy duty: 0.75 kW at 4.6 A (IEC) or 1.0 Hp at 4.6 A (UL). Light overload: 1.1 kW at 6.6 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000956685","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000956685 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}