{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000956708","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000956708","canonicalUrl":"https://aoctrl.com/abb/3AXD50000956708","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000956708","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH180 micro drive, 3AXD50000956708, 2.2 kW normal use (9.8 A), 230 V 3-phase, BACnet, frame R1, IP20, active production.","salesMarkdown":"## HVAC micro drive with BACnet The 3AXD50000956708: BACnet protocol is baked in, so it talks directly to a building management system without an external gateway. The drive includes a control unit, frame R1, IP20 enclosure, and a set of analog inputs (2), analog output (1), and digital I/O (4 DI / 2 DO) — enough for standalone fan or pump control with minimal external wiring. IE2 efficiency and a power factor of 0.98 keep electrical losses low; standby loss is just 7 W — a real consideration for energy tracking in continuous HVAC runs.","metaTitle":"ABB 3AXD50000956708 ACH180 Drive, 2.2 kW, BACnet","metaDescription":"Active ABB ACH180 micro drive, 2.2 kW normal use (9.8 A) on 230 V 3-phase. BACnet, IE2, IP20, frame R1. Sourced via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"SCIP":"a8a72b30-d5e5-4de6-b0f8-01a627cfc18e Finland","Altitude":"2000 m","Includes":"Control unit","Frame Size":"R1","Power Factor":"0.98","Sound dB (A)":"51.80 dB(A)","Standby Loss":"7 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"1","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 60 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP20","Apparent Power Output":"3.9 kV·A","Communication Protocol":"BACNET","Number of Digital In/Outputs":"4 / 2","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"2.2 kW","Output Current, Normal Use (In)":"9.8 A","Output Power, Heavy-Duty Use (PhD)":"1.5 kW","Output Current, Heavy-Duty Use (IhD)":"7.4 A","Output Power, Light-Overload Use (PlD)":"2.2 kW","Certificates and Declarations/RoHS Date":"20240110","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"9.3 A","Technical UL/Output Power, Normal Use (UL)":"2.0+ Hp","Technical UL/Output Current, Normal Use (UL)":"9.6 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"2.0 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"7.5 A","Technical UL/Output Power, Light-Overload Use (UL)":"2.0+ Hp","Technical UL/Output Current, Light-Overload Use (UL)":"9.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000956708","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000956708/alternatives.json"},"ai":{"faq":[{"question":"What is the SCIP number for this product?","answer":"The SCIP number is a8a72b30-d5e5-4de6-b0f8-01a627cfc18e Finland."},{"question":"What is the altitude rating?","answer":"The drive is rated for operation up to 2000 m altitude."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000956708","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000956708 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}