{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000956791","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000956791","canonicalUrl":"https://aoctrl.com/abb/3AXD50000956791","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000956791","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH180 series, LV AC micro drive module, 3AXD50000956791, 4.0 kW / 9.4 A normal use, 380-480 V 3-phase, IP20, BACnet, IE2.","salesMarkdown":"Normal-use output current (In) is 9.4 A; heavy-duty (IhD) is 7.2 A. For UL installations, the normal-use rating is 7.6 A, heavy-duty 6.3 A. Match your motor FLA against the appropriate duty cycle. Input voltage range is 380-480 V, frequency 47.5-63 Hz, so it covers 50 Hz and 60 Hz regions without a hardware change. Maximum ambient temperature is 60 °C, altitude 2000 m — above that, derate per the manual. Built-in I/O: 2 analog inputs, 1 analog output, 4 digital inputs, 2 digital outputs. No industrial Ethernet interface — BACnet is the sole fieldbus. That limits integration to BACnet MS/TP networks; if your controller speaks Modbus TCP or PROFINET, you need a different variant. ## Sourcing and procurement takeaway This is a current-production ABB drive, specified into a BOM for HVAC retrofit or new panel builds. The 3AXD50000956791 order code is the exact variant with BACnet and the R1 frame.","metaTitle":"ABB 3AXD50000956791 ACH180 Micro Drive, 4.0 kW, 9.4 A","metaDescription":"ABB ACH180-04S-09A4-4 micro drive, 4.0 kW / 9.4 A normal use, 380-480 V 3-phase, IP20, BACnet, IE2. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"5d07f008-496e-4abd-8f50-616cb485c791 Finland","Altitude":"2000 m","Includes":"Control unit","Frame Size":"R1","Power Factor":"0.98","Sound dB (A)":"50.90 dB(A)","Standby Loss":"10 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"1","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 60 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Apparent Power Output":"6.5 kV·A","Communication Protocol":"BACNET","Number of Digital In/Outputs":"4 / 2","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"4.0 kW","Output Current, Normal Use (In)":"9.4 A","Output Power, Heavy-Duty Use (PhD)":"3.0 kW","Output Current, Heavy-Duty Use (IhD)":"7.2 A","Output Power, Light-Overload Use (PlD)":"4.0 kW","Certificates and Declarations/RoHS Date":"20240110","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"8.9 A","Technical UL/Output Power, Normal Use (UL)":"5.0 Hp","Technical UL/Output Current, Normal Use (UL)":"7.6 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"3.0 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"6.3 A","Technical UL/Output Power, Light-Overload Use (UL)":"5.0 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"7.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000956791","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000956791/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does this drive have?","answer":"RoHS compliant per EU Directive 2011/65/EU (date 20240110). REACH declaration confirms substances above 0.1 mass percentage (date 20250905). SCIP number 5d07f008-496e-4abd-8f50-616cb485c791 Finland is registered. UL listing covers normal-use and heavy-duty ratings."},{"question":"What is the SCIP number for this drive?","answer":"SCIP number 5d07f008-496e-4abd-8f50-616cb485c791 Finland."},{"question":"What is the maximum altitude rating?","answer":"Rated for 2000 m altitude without derating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000956791","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000956791 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}