{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50000956838","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50000956838","canonicalUrl":"https://aoctrl.com/abb/3AXD50000956838","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50000956838","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH180-04S-033A-4, LV AC micro drive module for HVAC, 15 kW normal-use, 32.0 A at 400 V, IP20, BACnet, IE2.","salesMarkdown":"The ABB 3AXD50000956838 is an ACH180-04S-033A-4 LV AC micro drive module sized for HVAC applications. Normal-use output is 15 kW at 32.0 A on a 400 V three-phase supply (47.5–63 Hz). Heavy-duty use derates to 11 kW at 25.0 A; light-overload use holds 15 kW at 30.5 A. UL ratings at 460 V: 20 Hp / 27.0 A normal-use, 15 Hp / 21.0 A heavy-duty. Frame size R3, IP20, open type. ## Ratings & fit The normal-use current (32 A) is the spec to match against motor FLA for continuous duty. Heavy-duty current (25 A) governs for cyclic or high-start-torque loads. Power factor is 0.98. Standby loss is 23 W — relevant for panel thermal budgeting. Sound level is 66 dB(A). Altitude rating is 2000 m without derating. Analog inputs: 2; analog outputs: 1. Digital I/O: 4 inputs, 2 outputs. Communication is BACnet — no onboard Industrial Ethernet. This is a dedicated HVAC drive; no PROFINET or EtherCAT option in this order code.","metaTitle":"ABB ACH180-04S-033A-4 3AXD50000956838 LV AC Micro Drive, 15","metaDescription":"ABB 3AXD50000956838 ACH180-04S-033A-4 LV AC micro drive module, 15 kW normal-use, 32 A at 400 V, IP20, BACnet, IE2. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"SCIP":"323fe3e0-5686-4feb-b157-5ee9dbd9e7ac Finland","Altitude":"2000 m","Includes":"Control unit","Frame Size":"R3","Power Factor":"0.98","Sound dB (A)":"66.00 dB(A)","Standby Loss":"23 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"1","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 60 °C","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"380 ... 480 V","Degree of Protection":"IP20","Apparent Power Output":"22 kV·A","Communication Protocol":"BACNET","Number of Digital In/Outputs":"4 / 2","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"15 kW","Output Current, Normal Use (In)":"32.0 A","Output Power, Heavy-Duty Use (PhD)":"11 kW","Output Current, Heavy-Duty Use (IhD)":"25.0 A","Output Power, Light-Overload Use (PlD)":"15 kW","Certificates and Declarations/RoHS Date":"20240110","Certificates and Declarations/REACH Date":"20250905","Output Current, Light-Overload Use (IlD)":"30.5 A","Technical UL/Output Power, Normal Use (UL)":"20 Hp","Technical UL/Output Current, Normal Use (UL)":"27.0 A","Certificates and Declarations/RoHS Information":"Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019","Technical UL/Output Power, Heavy-Duty Use (UL)":"15 Hp","Certificates and Declarations/REACH Information":"True - contains substances > 0.1 mass percentage","Technical UL/Output Current, Heavy-Duty Use (UL)":"21.0 A","Technical UL/Output Power, Light-Overload Use (UL)":"20 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"27.0 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50000956838","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50000956838/alternatives.json"},"ai":{"faq":[{"question":"What is the SCIP number for this drive?","answer":"The SCIP number is 323fe3e0-5686-4feb-b157-5ee9dbd9e7ac Finland."},{"question":"What is the altitude rating?","answer":"Rated for operation up to 2000 m altitude without derating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50000956838","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50000956838 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}