{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50001002602","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50001002602","canonicalUrl":"https://aoctrl.com/abb/3AXD50001002602","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50001002602","rawCanonicalId":null},"summary":{"shortDescription":"ABB, ACH580-01 series, wall-mounted HVAC drive, 3AXD50001002602, 0.75 kW normal use, 4.7 A, 200-240 V 3-phase, IP66, NEMA 4X, BACnet.","salesMarkdown":"The IP66 / NEMA 4X enclosure means it handles washdowns, dust, and corrosive atmospheres without an additional cabinet — a direct fit for food-processing, wastewater, or outdoor HVAC installations where a standard IP20 drive would need a separate enclosure. ## Ratings that matter for the application Normal-use output (Pn) is 0.75 kW at 4.7 A; heavy-duty (PhD) drops to 0.55 kW at 3.5 A. The light-overload rating (PlD) matches normal use at 0.75 kW but carries a slightly lower current of 4.6 A — the difference is negligible for most fan and pump curves, but if you are sizing for a constant-torque load like a conveyor, use the heavy-duty line. The UL light-overload rating is 1 Hp at 4.6 A, which aligns with the IEC light-overload figure. Standby loss is 13 W — low enough that ventilation requirements are minimal in the enclosure. Power factor of 0.98 means the input current draw stays close to the real power, reducing upstream cable and breaker sizing compared to an older drive with a lower PF. ## Communication and I/O for HVAC integration BACnet is the onboard protocol, so this drive talks directly to a building management system without a gateway. Two analog inputs and two analog outputs handle duct static pressure sensors, temperature setpoints, or speed reference signals. Six digital inputs and three digital outputs cover start/stop, fault reset, and status feedback to the controller.","metaTitle":"ABB 3AXD50001002602 ACH580-01 HVAC Drive, 0.75 kW, IP66","metaDescription":"ABB ACH580-01 wall-mounted HVAC drive, 0.75 kW / 4.7 A normal use, 200-240 V 3-phase, IP66/NEMA 4X, BACnet, active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"Includes":"Control unit","Frame Size":"R1","Power Factor":"0.98","Standby Loss":"13 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type4X","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP66","Apparent Power Output":"1.9 kV·A","Communication Protocol":"BACNET","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"0.75 kW","Output Current, Normal Use (In)":"4.7 A","Output Power, Heavy-Duty Use (PhD)":"0.55 kW","Output Current, Heavy-Duty Use (IhD)":"3.5 A","Output Power, Light-Overload Use (PlD)":"0.75 kW","Output Current, Light-Overload Use (IlD)":"4.6 A","Technical UL/Output Power, Light-Overload Use (UL)":"1 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"4.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50001002602","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50001002602/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive?","answer":"Frame size is R1, which is the smallest frame in the ACH580-01 family. It is designed for wall mounting and occupies minimal panel space."},{"question":"Does this drive include the control unit?","answer":"Yes, the control unit is included with this order code. You receive a complete drive ready for commissioning without needing to order a separate operator panel or logic module."},{"question":"What enclosure rating does this drive have?","answer":"IP66 and NEMA 4X. It is suitable for washdown environments, outdoor installation, and corrosive atmospheres without an additional cabinet."},{"question":"What communication protocol does this drive support?","answer":"BACnet is the onboard protocol, enabling direct connection to building management systems without an external gateway."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50001002602","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50001002602 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}