{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50001002688","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50001002688","canonicalUrl":"https://aoctrl.com/abb/3AXD50001002688","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50001002688","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 wall-mounted HVAC drive, 3AXD50001002688, 0.75 kW / 1 Hp, 380-415 V, IP66, NEMA 4X, BACnet.","salesMarkdown":"The ABB 3AXD50001002688 is an ACH580-01 wall-mounted HVAC drive rated 0.75 kW output power at 2.6 A on 380-415 V three-phase input. It ships with the control unit included, frame size R1, and carries an IP66 / NEMA Type4X enclosure — meaning it can live on a wall in a washdown area or outdoors under a roof, no separate cabinet needed. BACnet is the onboard fieldbus; there is no industrial Ethernet port, so if you need Modbus TCP or PROFINET, plan on a gateway or a different variant. Normal-use output is 0.75 kW / 2.6 A; heavy-duty (constant torque) drops to 0.6 kW / 1.8 A. Light-overload use holds at 0.75 kW / 2.5 A. The UL listing shows 1 Hp / 2.1 A for light-overload — so if you are feeding a 1 Hp fan on 480 V, this drive fits. Standby loss is 14 W, power factor 0.98. Efficiency is IE2, which is baseline for this class; not premium, but fine for a fan or pump that runs continuously. ## I/O and control Two analog inputs and two analog outputs — enough for a speed reference and feedback from a pressure transducer. Six digital inputs and three digital outputs handle start/stop, fault reset, and a run status. The onboard BACnet port is the only communication interface; no Ethernet, no serial. The CR2032 lithium coin cell keeps the real-time clock alive for event logging. Ambient temperature limit is 40 °C; if your mechanical room hits 50 °C, derate or move it.","metaTitle":"ABB 3AXD50001002688 ACH580-01 Drive, 0.75 kW, IP66","metaDescription":"ABB 3AXD50001002688 ACH580-01 wall-mounted HVAC drive, 0.75 kW, 2.6 A, 400 V, IP66, NEMA 4X, BACnet, active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Includes":"Control unit","Frame Size":"R1","Power Factor":"0.98","Standby Loss":"14 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type4X","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP66","Apparent Power Output":"1.8 kV·A","Communication Protocol":"BACNET","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"0.75 kW","Output Current, Normal Use (In)":"2.6 A","Output Power, Heavy-Duty Use (PhD)":"0.6 kW","Output Current, Heavy-Duty Use (IhD)":"1.8 A","Output Power, Light-Overload Use (PlD)":"0.75 kW","Output Current, Light-Overload Use (IlD)":"2.5 A","Technical UL/Output Power, Light-Overload Use (UL)":"1 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"2.1 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50001002688","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50001002688/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to this drive in the same family?","answer":"There is no pin-compatible or drop-in alternative with the same ratings and enclosure. The ACH580-01 line offers different power levels and frame sizes, but this order code is unique for a 0.75 kW, IP66, BACnet drive."},{"question":"What does the drive include?","answer":"It includes the control unit — the drive ships as a complete wall-mounted unit with the control board and power stage integrated."},{"question":"What is the frame size?","answer":"Frame size R1 — the smallest in the ACH580-01 range, sized for 0.75 kW output."},{"question":"What compliance documentation is available?","answer":"The drive carries IP66 and NEMA Type4X enclosure ratings, UL listing for 1 Hp light-overload, and IE2 efficiency. Standard ABB documentation includes RoHS and REACH declarations; specific certificates are available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50001002688","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50001002688 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}