{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50001002701","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50001002701","canonicalUrl":"https://aoctrl.com/abb/3AXD50001002701","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50001002701","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 series, LV AC wall-mounted HVAC drive, 3AXD50001002701, 1.5 kW / 4 A normal duty, IP66, NEMA 4X, BACnet.","salesMarkdown":"The ABB 3AXD50001002701 is an ACH580-01 wall-mounted HVAC drive in frame size R1, rated 1.5 kW normal-use output at 4 A on a 380–415 V three-phase supply. It ships with the control unit included and carries IP66 / NEMA 4X protection, so it can mount directly on the wall in washdown or outdoor locations without an extra enclosure. Normal-use output is 1.5 kW / 4 A; heavy-duty use drops to 1.1 kW / 3.3 A. Light-overload use (the UL listing) is 2 Hp / 3.5 A at 500 V. The 0.98 power factor and 14 W standby loss mean it runs cool on the wall — no forced ventilation needed in a typical mechanical room. Ambient limit is 40 °C maximum; above that you'll need to derate or move the drive. The 47.5–63 Hz input frequency covers 50/60 Hz grids globally. ## I/O and comms Built-in BACnet on the control board — no option card needed for BMS integration. Two analog inputs and two analog outputs handle duct static pressure or discharge air temperature loops. Six digital inputs and three relay outputs cover start/stop, fault reset, and status feedback.","metaTitle":"ABB 3AXD50001002701 ACH580-01 HVAC Drive, 1.5 kW, IP66","metaDescription":"ABB 3AXD50001002701 ACH580-01 HVAC drive, 1.5 kW / 4 A normal duty, IP66, NEMA 4X, BACnet, active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Includes":"Control unit","Frame Size":"R1","Power Factor":"0.98","Standby Loss":"14 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type4X","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP66","Apparent Power Output":"2.8 kV·A","Communication Protocol":"BACNET","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"1.5 kW","Output Current, Normal Use (In)":"4 A","Output Power, Heavy-Duty Use (PhD)":"1.1 kW","Output Current, Heavy-Duty Use (IhD)":"3.3 A","Output Power, Light-Overload Use (PlD)":"1.5 kW","Output Current, Light-Overload Use (IlD)":"3.8 A","Technical UL/Output Power, Light-Overload Use (UL)":"2 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"3.5 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50001002701","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50001002701/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size and enclosure rating?","answer":"Frame size R1, wall-mounted, IP66 / NEMA 4X. Suitable for outdoor or washdown installation without an additional enclosure."},{"question":"What communication protocol does this drive support?","answer":"BACnet is built into the control board. No industrial Ethernet port is present on this variant."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50001002701","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50001002701 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}