{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50001002718","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50001002718","canonicalUrl":"https://aoctrl.com/abb/3AXD50001002718","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50001002718","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01-05A7-4+B063, LV AC wall-mounted HVAC drive, 2.2 kW / 5.6 A, 400 V, IP66, NEMA 4X, BACnet, frame R1.","salesMarkdown":"The 3AXD50001002718: The drive carries separate current ratings for three duty cycles: normal use at 5.6 A, light-overload at 5.3 A, and heavy-duty at 4 A. For a constant-torque HVAC load like a cooling tower fan, size against the heavy-duty figure — the 4 A rating gives you the thermal headroom for starting torque and sustained overload. The standby loss sits at 14 W, which matters for energy code compliance when the drive is idle but powered. Power factor is 0.98, so no external PF correction is needed for the drive itself. Efficiency is IE2 class, meeting the minimum for most commercial HVAC specs in Europe and APAC. ## Built-in I/O and BACnet for BAS integration This drive ships with 2 analog inputs, 2 analog outputs, and 6 digital inputs / 3 digital outputs — enough for a typical AHU or chiller pump sequence without an add-on I/O module. Communication is BACnet by default, which is the standard protocol for building automation systems. Note there is no onboard Industrial Ethernet port (0 hardware interfaces for that), so if your BAS backbone is BACnet/IP over Ethernet you will need the optional fieldbus adapter. The control unit is included in the package, so no separate ordering for the keypad.","metaTitle":"ABB 3AXD50001002718 ACH580 HVAC Drive, 2.2 kW, IP66","metaDescription":"ABB ACH580-01-05A7-4+B063 HVAC drive, 2.2 kW / 5.6 A, 400 V, IP66, NEMA 4X, BACnet, active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Includes":"Control unit","Frame Size":"R1","Power Factor":"0.98","Standby Loss":"14 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type4X","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP66","Apparent Power Output":"3.9 kV·A","Communication Protocol":"BACNET","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"2.2 kW","Output Current, Normal Use (In)":"5.6 A","Output Power, Heavy-Duty Use (PhD)":"1.5 kW","Output Current, Heavy-Duty Use (IhD)":"4 A","Output Power, Light-Overload Use (PlD)":"2.2 kW","Output Current, Light-Overload Use (IlD)":"5.3 A","Technical UL/Output Power, Light-Overload Use (UL)":"3 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"4.8 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50001002718","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50001002718/alternatives.json"},"ai":{"faq":[{"question":"What is the frame size of this drive?","answer":"Frame size R1, which is the smallest frame in the ACH580-01 series for this power class."},{"question":"Does this drive include a control unit?","answer":"Yes, the control unit is included with the order code — no separate keypad purchase needed."},{"question":"What communication protocol does this drive support?","answer":"BACnet is the onboard protocol. There is no built-in Industrial Ethernet port, so BACnet/IP over Ethernet requires an optional fieldbus adapter."},{"question":"What is the enclosure rating and where can it be mounted?","answer":"IP66 / NEMA Type 4X, wall-mounted. Suitable for outdoor or washdown environments without an additional cabinet."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50001002718","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50001002718 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}