{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50001002732","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50001002732","canonicalUrl":"https://aoctrl.com/abb/3AXD50001002732","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50001002732","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 series, 3AXD50001002732, LV AC wall-mounted HVAC drive, 4 kW / 9.4 A normal use, 380–415 V 3-phase, IP66/NEMA 4X, R1 frame, BACnet.","salesMarkdown":"The ABB 3AXD50001002732 is a wall-mounted HVAC drive in an R1 frame, rated 4 kW normal-use output at 9.4 A from a 380–415 V three-phase supply. It ships with the control unit included. Heavy-duty use is rated 3 kW at 7.2 A; light-overload use is 4 kW at 8.9 A. UL light-overload ratings are 3 Hp at 6.0 A. IP66 and NEMA Type 4X enclosure means this drive handles washdown environments, dust, and hose-directed water — common for rooftop HVAC units or food-processing air handlers. Maximum ambient temperature is 40 °C. Standby loss is 14 W, which matters for energy-code compliance on fan and pump drives that sit idle for long periods. Power factor is 0.98. Two analog inputs and two analog outputs are available for duct static pressure sensors or valve actuators. Six digital inputs and three digital outputs handle start/stop, fault reset, and status feedback. BACnet MS/TP is the onboard protocol — no option card needed for BAS integration. There is no industrial Ethernet port on this variant, so if the spec calls for BACnet/IP or Modbus TCP, that is a different order code. No direct pin-compatible alternative exists in the same family. If a different frame size or I/O count is needed, the order code changes.","metaTitle":"ABB 3AXD50001002732 ACH580-01 VFD, 4 kW, 9.4 A, IP66","metaDescription":"Active ABB ACH580-01 HVAC drive, 4 kW normal use, 9.4 A output, IP66/NEMA 4X, BACnet, wall-mount R1 frame. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Includes":"Control unit","Frame Size":"R1","Power Factor":"0.98","Standby Loss":"14 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type4X","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP66","Apparent Power Output":"6.5 kV·A","Communication Protocol":"BACNET","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"4 kW","Output Current, Normal Use (In)":"9.4 A","Output Power, Heavy-Duty Use (PhD)":"3 kW","Output Current, Heavy-Duty Use (IhD)":"7.2 A","Output Power, Light-Overload Use (PlD)":"4 kW","Output Current, Light-Overload Use (IlD)":"8.9 A","Technical UL/Output Power, Light-Overload Use (UL)":"3 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"6.0 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50001002732","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50001002732/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to 3AXD50001002732 in the ACH580 family?","answer":"There is no direct pin-compatible alternative within the same order code. The ACH580-01 is the standard wall-mount variant; changing frame size, I/O count, or enclosure rating requires a different order code."},{"question":"What does the 3AXD50001002732 include?","answer":"It includes the control unit. The drive ships with the control board and keypad interface, so no separate control unit order is needed."},{"question":"What is the frame size of this drive?","answer":"Frame size R1. This is the smallest frame in the ACH580-01 series, sized for 4 kW normal-use output."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50001002732","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50001002732 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}