{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50001002756","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50001002756","canonicalUrl":"https://aoctrl.com/abb/3AXD50001002756","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50001002756","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01-018A-4+B063, LV AC wall-mounted drive for HVAC, IEC: Pn 7.5 kW, 17 A, 400 V, UL: Pld 10 Hp, 14 A, 500 V, IP66, NEMA 4X, frame R2.","salesMarkdown":"The ABB 3AXD50001002756 is the order code for a wall-mounted drive sized for a 7.5 kW motor on a 380–415 V three-phase supply, delivering 17 A continuous in normal use. The IP66 / NEMA 4X enclosure makes it a direct mount in washdown or outdoor HVAC zones without a separate cabinet — the standby loss of 15 W stays inside the sealed box, so verify ambient stays under 40 °C on the back of the panel. Heavy-duty use derates the drive to 5.5 kW / 12.6 A; light-overload use holds at 7.5 kW but drops the current ceiling to 16.2 A. The UL light-overload line is 10 Hp at 14 A. Frame R2 is a wall-mount package. The control unit is included — no separate controller module to order. Two analog inputs and two analog outputs are on board; digital I/O counts six inputs and three outputs. BACnet is the built-in fieldbus; there is no second Ethernet interface, so if the site runs Modbus TCP or PROFINET, a separate option card is required. The lithium coin cell (CR2032, 220 mAh) keeps the real-time clock alive through power loss.","metaTitle":"3AXD50001002756 ABB ACH580-01-018A-4+B063 7.5 kW VFD, IP66,","metaDescription":"Active ABB ACH580-01 drive, 7.5 kW / 17 A, 380-415 VAC, IP66, NEMA 4X, BACnet, wall-mount frame R2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Includes":"Control unit","Frame Size":"R2","Power Factor":"0.98","Standby Loss":"15 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type4X","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP66","Apparent Power Output":"11.8 kV·A","Communication Protocol":"BACNET","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"7.5 kW","Output Current, Normal Use (In)":"17 A","Output Power, Heavy-Duty Use (PhD)":"5.5 kW","Output Current, Heavy-Duty Use (IhD)":"12.6 A","Output Power, Light-Overload Use (PlD)":"7.5 kW","Output Current, Light-Overload Use (IlD)":"16.2 A","Technical UL/Output Power, Light-Overload Use (UL)":"10 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"14 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50001002756","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50001002756/alternatives.json"},"ai":{"faq":[{"question":"What communication protocol does this drive support?","answer":"BACnet is the built-in protocol. The drive has no second industrial Ethernet interface, so a different fieldbus requires an option card."},{"question":"What is the ambient temperature limit for this drive?","answer":"The maximum ambient temperature rating is 40 °C. Above that, derating applies per the thermal curve."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50001002756","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50001002756 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}