{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50001002879","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50001002879","canonicalUrl":"https://aoctrl.com/abb/3AXD50001002879","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50001002879","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ580-01-060A-2+B063, LV AC wall-mounted drive, 15 kW / 60 A, 230 V, IP66, NEMA 4X, Frame R3.","salesMarkdown":"The 3AXD50001002879: Communication is CAN-only — no onboard Industrial Ethernet. If your plant runs PROFINET or EtherNet/IP, you'll need an option module. The drive has 2 analog inputs, 2 analog outputs, and 6 digital inputs / 3 digital outputs. That's enough for a basic pump start/stop with feedback and a pressure transducer; anything more complex and you're adding I/O. The control unit is included, so no separate order for that. Frame size is R3, wall-mounted. IP66 and NEMA 4X mean it's rated for washdown environments — install it outdoors or in a wet well without an extra cabinet, but keep ambient under 40 °C.","metaTitle":"ABB 3AXD50001002879 ACQ580-01-060A-2+B063 Drive, 15 kW, 60 A","metaDescription":"Active ABB ACQ580-01-060A-2+B063 LV AC drive, 15 kW normal use, 60 A, IP66, NEMA 4X, wall-mounted. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"Includes":"Control unit","Frame Size":"R3","Power Factor":"0.98","Standby Loss":"15 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type4X","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP66","Apparent Power Output":"23.9 kV·A","Communication Protocol":"CAN","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"15 kW","Output Current, Normal Use (In)":"60 A","Output Power, Heavy-Duty Use (PhD)":"11 kW","Output Current, Heavy-Duty Use (IhD)":"46.2 A","Output Power, Light-Overload Use (PlD)":"15 kW","Output Current, Light-Overload Use (IlD)":"59.4 A","Technical UL/Output Power, Light-Overload Use (UL)":"20 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"59 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50001002879","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50001002879/alternatives.json"},"ai":{"faq":[{"question":"What is included with the 3AXD50001002879?","answer":"The listing includes a Control unit. No other accessories or option modules are listed as included."},{"question":"What is the frame size of the 3AXD50001002879?","answer":"Frame size is R3."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50001002879","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50001002879 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}