{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50001003135","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50001003135","canonicalUrl":"https://aoctrl.com/abb/3AXD50001003135","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50001003135","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS580-01 wall-mounted drive, 4 kW normal use, 9.4 A, 380-415 V, IP66, NEMA 4X, frame R1, includes control unit.","salesMarkdown":"## Integrator's field note The ABB 3AXD50001003135 is a wall-mounted drive in frame R1, rated 4 kW normal use (9.4 A) on 380–415 V three-phase. The IP66 / NEMA 4X enclosure means it can sit directly on the machine frame or washdown area — no separate cabinet needed. Two analog inputs and two analog outputs are on board; digital I/O counts six inputs and three outputs. Communication is CAN only, so if the line uses Ethernet, plan on an external gateway or a different drive variant. ## Duty ratings Normal-use output is 4 kW / 9.4 A. Heavy-duty use drops to 3 kW / 7.2 A. Light-overload use is 4 kW / 8.9 A. UL light-overload rating is 3 Hp / 6.0 A at 500 V. Wall-mounted, frame R1. Ambient temperature limited to 40 °C maximum. Standby loss is 14 W — negligible for panel heat calculations but worth noting for sealed enclosures. Power factor is 0.98.","metaTitle":"ABB 3AXD50001003135 ACS580-01 Drive, 4 kW, 9.4 A, IP66","metaDescription":"ABB 3AXD50001003135 ACS580-01 wall-mounted drive, 4 kW normal use, 9.4 A output, IP66, NEMA 4X, frame R1. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Includes":"Control unit","Frame Size":"R1","Power Factor":"0.98","Standby Loss":"14 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type4X","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP66","Apparent Power Output":"6.5 kV·A","Communication Protocol":"CAN","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"4 kW","Output Current, Normal Use (In)":"9.4 A","Output Power, Heavy-Duty Use (PhD)":"3 kW","Output Current, Heavy-Duty Use (IhD)":"7.2 A","Output Power, Light-Overload Use (PlD)":"4 kW","Output Current, Light-Overload Use (IlD)":"8.9 A","Technical UL/Output Power, Light-Overload Use (UL)":"3 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"6.0 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50001003135","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50001003135/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this drive?","answer":"Normal-use output is 4 kW / 9.4 A at 380–415 V three-phase. Heavy-duty output is 3 kW / 7.2 A. Enclosure is IP66 / NEMA 4X. Frame size is R1."},{"question":"What communication protocol does this drive support?","answer":"CAN is the listed communication protocol; there are no industrial Ethernet interfaces."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50001003135","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50001003135 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}