{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50001004675","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50001004675","canonicalUrl":"https://aoctrl.com/abb/3AXD50001004675","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50001004675","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 series, LV AC wall-mounted HVAC drive, 3AXD50001004675, 3 kW / 12 A normal use, 200-240 V 3-phase input, IP66 / NEMA 4X, BACnet.","salesMarkdown":"The ABB 3AXD50001004675 is an ACH580-01 wall-mounted HVAC drive rated 3 kW normal-use output at 12 A, with heavy-duty capability at 2.2 kW / 7.5 A. It runs on 200-240 V three-phase input across 47.5-63 Hz. The package includes the control unit, so no separate controller card is needed — one order code lands a complete drive. The normal-use (light-overload) current is 11.8 A, while the heavy-duty line drops to 7.5 A. For UL-listed installations the light-overload output is 3 Hp at 10.6 A. The IE2 efficiency level and 0.98 power factor are typical for this class — the standby loss of 13 W matters if the drive idles for long periods in a multi-unit bank. IP66 and NEMA 4X rating means it handles washdown and outdoor installation without an extra cabinet. The maximum ambient is 40 °C — derate above that. Wall-mounted in frame size R1, so it fits a compact footprint. The lithium coin cell (CR2032, 220 mAh) keeps the real-time clock and parameter backup alive during power loss. Two analog inputs and two analog outputs cover the typical pressure/temperature/flow feedback loop. Six digital inputs and three digital outputs handle start/stop, fault reset, and run indication. BACnet is the onboard protocol — no option card needed for BMS integration. There is no industrial Ethernet interface, so if you need Modbus TCP or PROFINET, that requires a separate fieldbus adapter.","metaTitle":"ABB 3AXD50001004675 ACH580-01 HVAC Drive, 3 kW, 12 A, IP66","metaDescription":"ABB 3AXD50001004675 ACH580-01 HVAC drive, 3 kW normal use, 12 A output, IP66/NEMA 4X, BACnet, active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"Includes":"Control unit","Frame Size":"R1","Power Factor":"0.98","Standby Loss":"13 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type4X","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP66","Apparent Power Output":"4.8 kV·A","Communication Protocol":"BACNET","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"3 kW","Output Current, Normal Use (In)":"12 A","Output Power, Heavy-Duty Use (PhD)":"2.2 kW","Output Current, Heavy-Duty Use (IhD)":"7.5 A","Output Power, Light-Overload Use (PlD)":"3 kW","Output Current, Light-Overload Use (IlD)":"11.8 A","Technical UL/Output Power, Light-Overload Use (UL)":"3 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"10.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50001004675","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50001004675/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to this drive in the same family?","answer":"Within the ACH580-01 series, the closest peer would be a different frame size or voltage variant. For the same 200-240 V input and R1 frame, the normal-use current rating is the primary differentiator — this unit is 12 A; a lower-current variant would be a different order code. No pin-compatible drop-in exists because the I/O and control terminal layout is identical across the series, but the power stage changes with the current rating."},{"question":"What is included with this order code?","answer":"The order code includes the control unit as part of the drive assembly. No separate controller module is required."},{"question":"What is the frame size?","answer":"Frame size R1, which is the smallest in the ACH580-01 range. It is wall-mounted."},{"question":"What compliance documentation is available?","answer":"The drive carries UL listing (UL light-overload rating of 3 Hp at 10.6 A) and IEC ratings. The IP66 / NEMA 4X enclosure and IE2 efficiency level are documented. RoHS and REACH declarations are standard from ABB for this series."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50001004675","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50001004675 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}