{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50001057459","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50001057459","canonicalUrl":"https://aoctrl.com/abb/3AXD50001057459","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50001057459","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACS880-17-0800A-3, frame size R8i+R8i, 450 kW normal-use output, 800 A, 380–415 V 3-phase, IP22, NEMA Type 1.","salesMarkdown":"The ABB 3AXD50001057459 is an ACS880-17-0800A-3 drive in frame size R8i+R8i, rated for 450 kW normal-use output at 800 A on a 380–415 V 3-phase supply. Heavy-duty use drops to 315 kW / 598 A; light-overload use sits at 400 kW / 768 A. Frequency range covers 48–63 Hz. Three output ratings let you match the drive to the application without oversizing. Heavy-duty (PhD 315 kW, IhD 598 A) handles the extra thermal margin for high-start-torque or cyclic loads — crushers, extruders, or frequent starts. Light-overload (PlD 400 kW, IlD 768 A) fits variable-torque loads like fans or centrifugal pumps where peak demand is brief. Pick the duty class that matches your motor's actual profile, not the nameplate max. IP22 protection and NEMA Type 1 enclosure suit indoor, non-condensing environments. Operating humidity range 5–95% RH. The drive includes two BR2032 lithium coin cells for backup — factor battery replacement into long-term maintenance schedules.","metaTitle":"ABB 3AXD50001057459 ACS880-17 Drive, 450 kW / 800 A","metaDescription":"ABB ACS880-17-0800A-3 drive, 450 kW normal-use output, 800 A. Active production. Frame size R8i+R8i, 380–415 V 3-phase. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Frame Size":"R8i+R8i","Frequency (f)":"48 ... 63 Hz","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP22","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, BR2032, 2pcs, 3V, 200mAh, 3g","Output Power, Normal Use (Pn)":"450 kW","Output Current, Normal Use (In)":"800 A","Output Power, Heavy-Duty Use (PhD)":"315 kW","Output Current, Heavy-Duty Use (IhD)":"598 A","Output Power, Light-Overload Use (PlD)":"400 kW","Output Current, Light-Overload Use (IlD)":"768 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50001057459","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50001057459/alternatives.json"},"ai":{"faq":[{"question":"What are the normal-use and heavy-duty output ratings?","answer":"Normal-use output is 450 kW at 800 A; heavy-duty output is 315 kW at 598 A."},{"question":"What input voltage and frequency does this drive accept?","answer":"Input voltage is 380–415 V 3-phase, frequency 48–63 Hz."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50001057459","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50001057459 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}