{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50001057619","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50001057619","canonicalUrl":"https://aoctrl.com/abb/3AXD50001057619","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50001057619","rawCanonicalId":null},"summary":{"shortDescription":"ABB, ACS880-37 series, 3AXD50001057619, 450 kW / 800 A normal use, IP22, NEMA Type 1, frame R8i+R8i.","salesMarkdown":"## What this is and what it drives The 3AXD50001057619: Three-phase input at 380–415 V, 48–63 Hz. Heavy-duty rating is 315 kW / 598 A; light-overload rating is 400 kW / 768 A. That spread covers pump, fan, and conveyor profiles — normal use for constant torque, heavy-duty for high-starting-torque loads, light-overload for variable-torque centrifugal machines. Operating humidity range is 5–95% RH, altitude rated to 1000 m without derating. The drive carries two lithium coin cells (BR2032, 3 V, 200 mAh) for real-time-clock backup. If the unit has been in storage, those may need replacement before commissioning — factor that into your spares plan. WEEE category 4 (large equipment >50 cm) applies for end-of-life disposal compliance.","metaTitle":"ABB 3AXD50001057619 ACS880-37-0800A-3, 450 kW, 800 A","metaDescription":"ABB 3AXD50001057619 ACS880-37-0800A-3 drive, 450 kW normal use, 800 A output. Active production. Frame size R8i+R8i. 3-phase, 380-415 V input. IP22, NEMA Type 1. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Altitude":"1000 m","Frame Size":"R8i+R8i","Frequency (f)":"48 ... 63 Hz","WEEE Category":"4. Large Equipment (Any External Dimension More Than 50 cm)","lifecycle_stage":"current","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP22","Operating Humidity (RHamβ)":"5 ... 95","Multiple Battery Information":"Lithium Coin, BR2032, 2pcs, 3V, 200mAh, 3g","Output Power, Normal Use (Pn)":"450 kW","Output Current, Normal Use (In)":"800 A","Output Power, Heavy-Duty Use (PhD)":"315 kW","Output Current, Heavy-Duty Use (IhD)":"598 A","Output Power, Light-Overload Use (PlD)":"400 kW","Output Current, Light-Overload Use (IlD)":"768 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50001057619","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50001057619/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this drive?","answer":"Normal-use output is 450 kW / 800 A; heavy-duty is 315 kW / 598 A; light-overload is 400 kW / 768 A. Input is 3-phase 380–415 V, 48–63 Hz."},{"question":"What is the frame size and enclosure type?","answer":"Frame size is R8i+R8i. Enclosure is IP22 with NEMA Type 1, suitable for indoor clean electrical rooms."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50001057619","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50001057619 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}