{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50001076405","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50001076405","canonicalUrl":"https://aoctrl.com/abb/3AXD50001076405","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50001076405","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-31 ultra-low harmonic drive, 3-phase, 208-240 V, 20 Hp light-overload, 59.4 A, IP21, Type 1, frame R6.","salesMarkdown":"The 3AXD50001076405: Frame size R6, IP21 enclosure, NEMA Type 1 — sized for a standard wall-mount install with gland-plate clearance for incoming power and motor leads. 50/60 Hz input frequency, no derating needed across the line range. The 59.4 A light-overload figure is the UL-listed continuous output current at 20 Hp. That is the number to match against your motor FLA for a standard variable-torque HVAC load — fan or pump curves. The 208-240 V three-phase input is a narrow band; confirm your site supply lands inside that range before committing the BOM line. IP21 and NEMA Type 1 cover indoor installation with some drip protection — no washdown or outdoor rating. Frame R6 means the mounting footprint and conduit knockouts follow the ABB R6 pattern; verify gland-plate layout against your existing panel cutout.","metaTitle":"ABB 3AXD50001076405 ACH580-31 Drive, 20 Hp, 59.4 A, 230 V","metaDescription":"ABB 3AXD50001076405 ACH580-31 ultra-low harmonic drive, 3-phase, 208-240 V input, 20 Hp light-overload, 59.4 A output, IP21, Type 1, frame R6. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"title":"3AXD50001076405","Frame Size":"R6","description":"Wall-mounted ultra-low harmonic drive for HVAC, UL: Pld 20 Hp, 59.4 A, 230 V (ACH580-31-059A-2)","Frequency (f)":"50/60 Hz","lifecycle_stage":"current","Number of Phases":"3-phase","Enclosure Type NEMA":"Type1","Input Voltage (Uin)":"208 ... 240 V","Degree of Protection":"IP21","Technical UL/Output Power, Light-Overload Use (UL)":"20 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"59.4 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8b87beb82b57fa9fd842386c893a12c8.pdf","sourceUrl":"https://www.abb.com/global/en/products/3axd50001076405"},"ai":{"faq":[{"question":"What is the frame size of this drive?","answer":"Frame size R6."},{"question":"What is the input voltage and frequency range?","answer":"Three-phase 208-240 V, 50/60 Hz."},{"question":"What is the light-overload output rating?","answer":"20 Hp at 59.4 A continuous, UL listed."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50001076405","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50001076405 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}