{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50001109516","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50001109516","canonicalUrl":"https://aoctrl.com/abb/3AXD50001109516","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50001109516","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ580-01 series, LV AC wall-mounted drive, 3AXD50001109516, 1.1 kW / 3.3 A, 400 V, IP66, NEMA Type4X, CAN communication, IE2.","salesMarkdown":"## Duty ratings and overload capability The 3AXD50001109516: Normal-use output is 1.1 kW / 3.3 A; heavy-duty use is 0.8 kW / 2.6 A. Light-overload use matches the normal-use power at 1.1 kW but draws 3.1 A. Under UL listing, light-overload output is 2 Hp at 3 A. The drive accepts 47.5–63 Hz input and is rated for a maximum ambient of 40 °C. Two analog inputs and two analog outputs are available for process signals. Six digital inputs and three digital outputs handle discrete control. Communication is via CAN protocol; there is no onboard Industrial Ethernet interface. A lithium coin cell (CR2032, 220 mAh, 3 V) backs the real-time clock.","metaTitle":"ABB 3AXD50001109516 ACQ580-01 drive, 1.1 kW, IP66, Type4X","metaDescription":"Active ABB ACQ580-01 wall-mounted drive, 1.1 kW, 3.3 A, 400 V, IP66, NEMA Type4X, CAN protocol, IE2 efficiency. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Includes":"Control unit","Power Factor":"0.98","Standby Loss":"14 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type4X","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP66","Apparent Power Output":"2.3 kV·A","Communication Protocol":"CAN","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"1.1 kW","Output Current, Normal Use (In)":"3.3 A","Output Power, Heavy-Duty Use (PhD)":"0.8 kW","Output Current, Heavy-Duty Use (IhD)":"2.6 A","Output Power, Light-Overload Use (PlD)":"1.1 kW","Output Current, Light-Overload Use (IlD)":"3.1 A","Technical UL/Output Power, Light-Overload Use (UL)":"2 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"3 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50001109516","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50001109516/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the 3AXD50001109516?","answer":"Normal-use output is 1.1 kW at 3.3 A from a 380–415 V three-phase supply. Heavy-duty output is 0.8 kW at 2.6 A. The drive is IP66 / NEMA Type4X, wall-mounted, with CAN communication and IE2 efficiency."},{"question":"What does the 3AXD50001109516 include?","answer":"It includes a control unit."},{"question":"What is the power factor of the 3AXD50001109516?","answer":"The power factor is 0.98."},{"question":"What compliance documentation is available for the 3AXD50001109516?","answer":"The evidence does not list specific compliance documents (RoHS, REACH, UL, IEC) for this order code. The drive carries a UL output rating of 2 Hp / 3 A under light-overload use, indicating UL involvement."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50001109516","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50001109516 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}