{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50001109585","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50001109585","canonicalUrl":"https://aoctrl.com/abb/3AXD50001109585","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50001109585","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACQ580-01 wall-mounted LV AC drive, 3-phase 380-415 V input, 11 kW normal duty, 25 A output, IP66 / NEMA 4X, IE2 efficiency, includes control unit.","salesMarkdown":"The ABB 3AXD50001109585 is a wall-mounted LV AC drive, IEC-rated 11 kW normal duty at 25 A on 400 V three-phase, with a heavy-duty rating of 7.5 kW at 17 A. It is built for water and wastewater applications, carrying an IP66 / NEMA 4X enclosure that handles washdown environments directly. The normal-duty current of 25 A (In) is the continuous rating for pump and fan profiles; the light-overload rating of 23.8 A (IlD) at 11 kW matches the same power but with a slightly lower current headroom. Heavy-duty use at 17 A (IhD) covers constant-torque loads like screw pumps or conveyors. The UL listing shows 15 Hp at 23 A on 460 V, so the drive fits both IEC and North American motor frames without derating. Power factor is 0.98, which means the drive presents near-unity power factor to the line — good for installations where utility penalties apply. Standby loss sits at 15 W, low enough to leave the drive powered continuously in a panel without significant heat buildup. Communication is CAN-based; there are no onboard industrial Ethernet ports. If you need PROFINET or EtherNet/IP, plan for an external gateway or option module. IP66 / NEMA 4X means the drive is dust-tight and hose-down rated — suitable for outdoor installation or washdown zones in water treatment, food processing, or marine applications. Maximum ambient temperature is 40 °C; above that, derate the output current. Wall-mounted, so it saves floor space but needs clearance around the enclosure for airflow. The control unit is included, so no separate order for the keypad or logic board. The drive has 2 analog inputs and 2 analog outputs, plus 6 digital inputs and 3 digital outputs — enough for a basic pump control loop with feedback and a few status signals. A CR2032 lithium coin cell (220 mAh, 3 V) backs up the real-time clock and parameter memory.","metaTitle":"ABB 3AXD50001109585 ACQ580-01 drive, 11 kW, IP66, NEMA 4X","metaDescription":"ABB ACQ580-01 LV AC wall-mounted drive, 11 kW normal duty, 25 A, IP66, NEMA 4X, IE2. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Includes":"Control unit","Power Factor":"0.98","Standby Loss":"15 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type4X","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP66","Apparent Power Output":"17.3 kV·A","Communication Protocol":"CAN","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"11 kW","Output Current, Normal Use (In)":"25 A","Output Power, Heavy-Duty Use (PhD)":"7.5 kW","Output Current, Heavy-Duty Use (IhD)":"17 A","Output Power, Light-Overload Use (PlD)":"11 kW","Output Current, Light-Overload Use (IlD)":"23.8 A","Technical UL/Output Power, Light-Overload Use (UL)":"15 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"23 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50001109585","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50001109585/alternatives.json"},"ai":{"faq":[{"question":"What does the 'Includes Control unit' mean?","answer":"The drive ships with the control unit (keypad and logic board) included, so no separate accessory order is needed for basic operation."},{"question":"What is the power factor and standby loss?","answer":"Power factor is 0.98. Standby loss is 15 W."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50001109585","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50001109585 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}