{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50001109639","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50001109639","canonicalUrl":"https://aoctrl.com/abb/3AXD50001109639","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50001109639","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 wall-mounted HVAC drive, 1.1 kW / 6.7 A normal use, 200–240 V 3-phase, IP66, NEMA 4X, BACnet.","salesMarkdown":"The ABB 3AXD50001109639 is an ACH580-01 wall-mounted HVAC drive rated for 1.1 kW normal-use output (Pn) at 6.7 A (In) on a 200–240 V three-phase supply. Heavy-duty use (PhD) is 0.75 kW at 4.6 A (IhD); light-overload use (PlD) matches the normal-use power at 1.1 kW, 6.6 A (IlD). UL light-overload rating is 1.5 Hp at 6.6 A. Power factor is 0.98; standby loss is 13 W. Built-in BACnet communication (no industrial Ethernet interface) and 2 analog inputs plus 2 analog outputs suit it for building management system integration. Digital I/O count is 6 inputs and 3 outputs. Enclosure is IP66 / NEMA Type4X, wall-mounted, rated for ambient temperatures up to 40 °C. Efficiency class is IE2. The drive includes a control unit and a lithium coin cell (CR2032, 220 mAh, 3 V) for backup. Frequency range is 47.5–63 Hz.","metaTitle":"ABB 3AXD50001109639 ACH580 HVAC Drive, 1.1 kW, 6.7 A, 230 V","metaDescription":"Active ABB ACH580-01 wall-mounted drive for HVAC. 1.1 kW normal use, 6.7 A output, 200-240 V 3-phase. IP66, NEMA 4X, BACnet, IE2. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"Includes":"Control unit","Power Factor":"0.98","Standby Loss":"13 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type4X","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP66","Apparent Power Output":"2.7 kV·A","Communication Protocol":"BACNET","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"1.1 kW","Output Current, Normal Use (In)":"6.7 A","Output Power, Heavy-Duty Use (PhD)":"0.75 kW","Output Current, Heavy-Duty Use (IhD)":"4.6 A","Output Power, Light-Overload Use (PlD)":"1.1 kW","Output Current, Light-Overload Use (IlD)":"6.6 A","Technical UL/Output Power, Light-Overload Use (UL)":"1.5 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"6.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50001109639","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50001109639/alternatives.json"},"ai":{"faq":[{"question":"What is included with this drive?","answer":"It includes a control unit and a CR2032 lithium coin cell (220 mAh, 3 V)."},{"question":"What is the power factor of this drive?","answer":"The power factor is 0.98."},{"question":"What compliance documentation is available for this drive?","answer":"The evidence does not list specific compliance documents (RoHS, REACH, UL, IEC). The drive carries a UL light-overload rating (1.5 Hp, 6.6 A) and is designed to IEC standards per the description."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50001109639","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50001109639 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}