{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50001109677","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50001109677","canonicalUrl":"https://aoctrl.com/abb/3AXD50001109677","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50001109677","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01-025A-2+B063+F253, LV AC wall-mounted drive for HVAC, 5.5 kW / 7.5 Hp, 24.5 A, 200-240 V, IP66, NEMA 4X, includes control unit.","salesMarkdown":"The 3AXD50001109677 is an ABB ACH580-01-025A-2+B063+F253 LV AC wall-mounted drive built for HVAC duty. Normal-use output is 5.5 kW at 24.5 A on a 200-240 V three-phase supply. Heavy-duty use drops to 4 kW and 16.7 A; light-overload use holds at 5.5 kW and 24.2 A. UL light-overload rating is 7.5 Hp at 24 A. Power factor sits at 0.98, standby loss at 14 W. Efficiency class IE2. Frequency range 47.5-63 Hz. Enclosure is IP66 / NEMA Type4X, wall-mounted, rated for ambient up to 40 °C. Includes control unit with 2 analog inputs, 2 analog outputs, 6 digital inputs, 3 digital outputs, and BACnet communication.","metaTitle":"ABB 3AXD50001109677 ACH580 HVAC Drive, 5.5 kW, 24.5 A, IP66","metaDescription":"ABB ACH580-01-025A-2 wall-mounted drive, 5.5 kW / 7.5 Hp, 24.5 A, 200-240 V, IP66, NEMA 4X, BACnet, active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"Includes":"Control unit","Power Factor":"0.98","Standby Loss":"14 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type4X","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP66","Apparent Power Output":"9.8 kV·A","Communication Protocol":"BACNET","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"5.5 kW","Output Current, Normal Use (In)":"24.5 A","Output Power, Heavy-Duty Use (PhD)":"4 kW","Output Current, Heavy-Duty Use (IhD)":"16.7 A","Output Power, Light-Overload Use (PlD)":"5.5 kW","Output Current, Light-Overload Use (IlD)":"24.2 A","Technical UL/Output Power, Light-Overload Use (UL)":"7.5 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"24 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50001109677","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50001109677/alternatives.json"},"ai":{"faq":[{"question":"What enclosure protection does it carry?","answer":"IP66 and NEMA Type4X, wall-mounted."},{"question":"What communication protocol is built in?","answer":"BACnet is listed. No Industrial Ethernet interfaces are included."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50001109677","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50001109677 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}