{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50001109707","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50001109707","canonicalUrl":"https://aoctrl.com/abb/3AXD50001109707","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50001109707","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 wall-mounted HVAC drive, 3-phase 200–240 V, 15 kW / 20 HP, 60 A normal use, IP66/NEMA 4X, BACnet, IE2 efficiency, includes control unit.","salesMarkdown":"The ABB 3AXD50001109707 is an ACH580-01 wall-mounted HVAC drive for 3-phase 200–240 V supplies. Normal-use rating is 15 kW / 60 A; heavy-duty use drops to 11 kW / 46.2 A. Light-overload use matches the normal-use power at 15 kW / 59.4 A. UL light-overload rating is 20 HP / 59 A. Enclosure is IP66 / NEMA Type4X, rated for washdown and outdoor installation. Ambient temperature limited to 40 °C maximum. Efficiency class IE2. Power factor 0.98. Standby loss 15 W. Built-in BACnet communication. Two analog inputs and two analog outputs. Six digital inputs, three digital outputs. No onboard Ethernet port.","metaTitle":"ABB 3AXD50001109707 ACH580 HVAC Drive, 15 kW, 60 A, IP66","metaDescription":"Active ABB ACH580-01 HVAC drive, 15 kW / 20 HP, 60 A, IP66/NEMA 4X, BACnet, IE2. Sourced to order. RFQ for lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"Includes":"Control unit","Power Factor":"0.98","Standby Loss":"15 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type4X","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP66","Apparent Power Output":"23.9 kV·A","Communication Protocol":"BACNET","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"15 kW","Output Current, Normal Use (In)":"60 A","Output Power, Heavy-Duty Use (PhD)":"11 kW","Output Current, Heavy-Duty Use (IhD)":"46.2 A","Output Power, Light-Overload Use (PlD)":"15 kW","Output Current, Light-Overload Use (IlD)":"59.4 A","Technical UL/Output Power, Light-Overload Use (UL)":"20 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"59 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50001109707","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50001109707/alternatives.json"},"ai":{"faq":[{"question":"What does the drive include?","answer":"The listing includes the control unit. The drive is a complete ACH580-01 wall-mounted unit with BACnet and I/O."},{"question":"What enclosure protection does it have?","answer":"IP66 and NEMA Type4X. Suitable for outdoor and washdown environments. Ambient temperature maximum 40 °C."},{"question":"What communication protocol does it support?","answer":"BACnet is built in. No Ethernet port on this variant."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50001109707","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50001109707 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}