{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50001109745","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50001109745","canonicalUrl":"https://aoctrl.com/abb/3AXD50001109745","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50001109745","rawCanonicalId":null},"summary":{"shortDescription":"ABB, ACH580-01 series, LV AC wall-mounted drive, 3AXD50001109745, 2.2 kW / 5.6 A normal use, 400 V, IP66, Type 4X, BACnet.","salesMarkdown":"The 3AXD50001109745: IP66 and NEMA Type 4X enclosure means this drive handles washdown and outdoor installation without a secondary cabinet. Ambient limit is 40 °C. Wall-mounted, so plan for conduit entries from below and clearance for the heatsink fins. BACnet on the serial port — no Industrial Ethernet interface on this variant. The drive carries 2 analog inputs, 2 analog outputs, 6 digital inputs, and 3 digital outputs. That's enough for a basic HVAC fan or pump loop without an expansion module. ## Standby and power quality Standby loss is 14 W, which matters for continuous-duty installations where the drive is powered but the motor is idle. Power factor is 0.98, typical for an active front-end or well-tuned drive.","metaTitle":"ABB 3AXD50001109745 ACH580-01 VFD, 2.2 kW, 5.6 A, IP66","metaDescription":"ABB 3AXD50001109745 ACH580-01 wall-mounted drive, 2.2 kW normal use, 5.6 A, 400 V, IP66, Type 4X, BACnet. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Includes":"Control unit","Power Factor":"0.98","Standby Loss":"14 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type4X","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP66","Apparent Power Output":"3.9 kV·A","Communication Protocol":"BACNET","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"2.2 kW","Output Current, Normal Use (In)":"5.6 A","Output Power, Heavy-Duty Use (PhD)":"1.5 kW","Output Current, Heavy-Duty Use (IhD)":"4 A","Output Power, Light-Overload Use (PlD)":"2.2 kW","Output Current, Light-Overload Use (IlD)":"5.3 A","Technical UL/Output Power, Light-Overload Use (UL)":"3 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"4.8 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50001109745","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50001109745/alternatives.json"},"ai":{"faq":[{"question":"What does 'Includes Control unit' mean for this order code?","answer":"The order code 3AXD50001109745 includes the control unit as part of the drive package — it is not a bare power stage. The control unit is integrated, not a separate purchase."},{"question":"What is the power factor of this drive?","answer":"The power factor is listed at 0.98."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50001109745","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50001109745 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}