{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50001109776","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50001109776","canonicalUrl":"https://aoctrl.com/abb/3AXD50001109776","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50001109776","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 wall-mounted HVAC drive, 3AXD50001109776, 5.5 kW / 12.6 A normal duty, 380-415 V 3-phase, IP66/Type4X, includes control unit.","salesMarkdown":"## Input and environmental specs The 3AXD50001109776: Input voltage range is 380 to 415 V three-phase, 47.5 to 63 Hz. The drive is IP66-rated with a NEMA Type 4X enclosure, suitable for washdown or outdoor mounting without an additional cabinet. Ambient temperature limit is 40 °C. ## Efficiency and standby losses Rated IE2 efficiency level. Standby loss is 14 W, which matters for continuous HVAC fan or pump applications where the drive idles but stays powered — keep that in the energy budget for the panel's thermal design. Built-in BACnet communication protocol for building automation integration. Two analog inputs and two analog outputs are available for sensor feedback or setpoint control. Digital I/O consists of 6 inputs and 3 outputs.","metaTitle":"ABB 3AXD50001109776 ACH580 HVAC Drive, 5.5 kW, 12.6 A, IP66","metaDescription":"ABB ACH580-01 wall-mounted drive for HVAC. 5.5 kW (7.5 Hp) normal duty, 12.6 A, 380-415 V, IP66/Type4X. BACnet, analog I/O, IE2. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Includes":"Control unit","Power Factor":"0.98","Standby Loss":"14 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type4X","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP66","Apparent Power Output":"8.7 kV·A","Communication Protocol":"BACNET","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"5.5 kW","Output Current, Normal Use (In)":"12.6 A","Output Power, Heavy-Duty Use (PhD)":"4 kW","Output Current, Heavy-Duty Use (IhD)":"9.4 A","Output Power, Light-Overload Use (PlD)":"5.5 kW","Output Current, Light-Overload Use (IlD)":"12 A","Technical UL/Output Power, Light-Overload Use (UL)":"7.5 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"12 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50001109776","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50001109776/alternatives.json"},"ai":{"faq":[{"question":"What is 3AXD50001109776's listed includes (Control unit) on this component line?","answer":"The listing includes a control unit as part of the drive assembly."},{"question":"What is 3AXD50001109776's listed power factor (0.98) on this component line?","answer":"The power factor is listed as 0.98, which is typical for a modern drive with active rectification or a high displacement factor under rated load."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50001109776","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50001109776 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}