{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50001109790","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50001109790","canonicalUrl":"https://aoctrl.com/abb/3AXD50001109790","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50001109790","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 series, LV AC wall-mounted HVAC drive, 3AXD50001109790, 11 kW / 25 A normal duty, IP66, NEMA 4X, BACnet.","salesMarkdown":"Normal-use output current is 25 A (In) — that's the continuous rating for a standard pump or fan load. Light-overload use (PlD) also runs at 11 kW but draws 23.8 A, slightly less headroom. Heavy-duty use (PhD) drops to 7.5 kW / 17 A, which is the rating to use if the load cycles hard or runs near full torque at low speed. The UL light-overload line is 15 Hp at 23 A, 500 V — match that to your local code if the job is under NEC. Standby loss is 15 W — negligible for energy tracking but worth noting if the drive sits on a UPS-backed circuit. Efficiency is IE2 class, which is the baseline for HVAC drives in most markets; no premium-efficiency adder here. ## I/O and fieldbus for the controls integrator The drive carries 2 analog inputs and 2 analog outputs — enough for a speed reference from a BMS and a feedback signal. Digital I/O counts 6 inputs and 3 outputs, which covers start/stop, fault reset, and a run-status relay back to the controller. Communication is BACnet out of the box; no option card needed for BAS integration. The control unit is included, so the drive ships ready to commission — no separate control panel to order. The lithium coin cell (CR2032, 220 mAh) keeps the real-time clock alive through a power loss. That means this order code is still the current production variant for the ACH580-01 11 kW IP66 BACnet configuration. No successor to track; no cross-reference needed.","metaTitle":"ABB 3AXD50001109790 ACH580 HVAC Drive, 11 kW, 25 A, IP66","metaDescription":"ABB 3AXD50001109790 ACH580-01 wall-mounted HVAC drive. 11 kW normal duty, 25 A output, IP66/NEMA 4X. BACnet. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Includes":"Control unit","Power Factor":"0.98","Standby Loss":"15 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type4X","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP66","Apparent Power Output":"17.3 kV·A","Communication Protocol":"BACNET","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"11 kW","Output Current, Normal Use (In)":"25 A","Output Power, Heavy-Duty Use (PhD)":"7.5 kW","Output Current, Heavy-Duty Use (IhD)":"17 A","Output Power, Light-Overload Use (PlD)":"11 kW","Output Current, Light-Overload Use (IlD)":"23.8 A","Technical UL/Output Power, Light-Overload Use (UL)":"15 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"23 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50001109790","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50001109790/alternatives.json"},"ai":{"faq":[{"question":"What does the IP66 rating mean for installation?","answer":"IP66 and NEMA 4X mean the drive is dust-tight and protected against hose-directed water and corrosion. It mounts directly on a wall or rooftop without an extra enclosure — suitable for food processing washdowns, chemical plants, and outdoor HVAC units."},{"question":"What communication protocol does this drive use?","answer":"BACnet is the onboard protocol, so it connects directly to building automation systems without an add-on gateway or option card."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50001109790","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50001109790 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}