{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50001109806","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50001109806","canonicalUrl":"https://aoctrl.com/abb/3AXD50001109806","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50001109806","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH580-01 series LV AC wall-mounted drive, 15 kW / 32 A normal use, IP66 Type 4X, BACnet, IE2 efficiency.","salesMarkdown":"The 3AXD50001109806: Communication is BACnet out of the box, so it drops straight into a building automation network. Power factor sits at 0.98, and standby loss is 16 W — numbers that matter when the facility engineer is tracking energy spend per VFD. ## Ratings that drive the selection Three duty points cover the load profile: normal-use (15 kW, 32 A), light-overload (15 kW, 30.4 A), and heavy-duty (11 kW, 24.6 A). The UL light-overload rating is 20 Hp at 27 A. Match the fan or pump curve to the right row — heavy-duty gives you headroom for starting torque or momentary overloads. Wall-mounted, IP66, NEMA Type 4X. That means rain, hose-down, dust, and corrosion resistance — install it on the roof, beside the cooling tower, or in a food-processing wash bay. No rain hood required in most cases, though direct sun might call for a shade. The drive ships with a control unit included (the Includes field lists it). Onboard analog I/O: 2 inputs, 2 outputs. Digital I/O: 6 inputs, 3 outputs. No onboard Ethernet port — Industrial Ethernet count is 0 — so BACnet is the fieldbus path.","metaTitle":"ABB 3AXD50001109806 ACH580 HVAC Drive, 15 kW, 32 A, IP66","metaDescription":"Active ABB ACH580-01 wall-mounted drive for HVAC. 15 kW normal-use (32 A), 11 kW heavy-duty. IP66 Type 4X, BACnet, IE2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Includes":"Control unit","Power Factor":"0.98","Standby Loss":"16 W","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Wall-mounted","Analog Outputs":"2","lifecycle_stage":"current","Efficiency Level":"IE2","Number of Phases":"3-phase","Temperature Rating":"Maximum 40 °C","Enclosure Type NEMA":"Type4X","Input Voltage (Uin)":"380 ... 415 V","Degree of Protection":"IP66","Apparent Power Output":"22.2 kV·A","Communication Protocol":"BACNET","Multiple Battery Information":"Lithium Coin; CR2032; 220 mAh; 3 V; 1 pc; 3 g","Number of Digital In/Outputs":"6 / 3","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"15 kW","Output Current, Normal Use (In)":"32 A","Output Power, Heavy-Duty Use (PhD)":"11 kW","Output Current, Heavy-Duty Use (IhD)":"24.6 A","Output Power, Light-Overload Use (PlD)":"15 kW","Output Current, Light-Overload Use (IlD)":"30.4 A","Technical UL/Output Power, Light-Overload Use (UL)":"20 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"27 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50001109806","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50001109806/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this drive?","answer":"Normal-use output is 15 kW at 32 A; heavy-duty is 11 kW at 24.6 A. Input is 380–415 V, 3-phase, 47.5–63 Hz. IP66 enclosure, BACnet communication, IE2 efficiency."},{"question":"What does the 'Includes' field list for this drive?","answer":"The listing includes a control unit."},{"question":"What is the power factor of the 3AXD50001109806?","answer":"The power factor is 0.98."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50001109806","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50001109806 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}