{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3AXD50001110079","brand":"ABB","brandSlug":"abb","productSlug":"3AXD50001110079","canonicalUrl":"https://aoctrl.com/abb/3AXD50001110079","factsUrl":"https://aoctrl.com/api/mcp/products/3AXD50001110079","rawCanonicalId":null},"summary":{"shortDescription":"ABB ACH180 series micro drive, order code 3AXD50001110079, 0.75 kW normal-use output, 4.8 A, 200-240 V three-phase, IP20, BACnet communication, frame size R0.","salesMarkdown":"The ABB 3AXD50001110079 is an ACH180-series micro drive rated for 0.75 kW normal-use output at 4.8 A on a 200-240 V three-phase supply. Heavy-duty use derates to 0.55 kW and 3.2 A — sized for a constant-torque load like a small conveyor or positive-displacement pump. Light-overload use holds at 0.75 kW, 4.6 A, matching the normal-use power but with slightly lower current headroom. UL ratings land at 1 Hp normal-use and light-overload, 0.75 Hp heavy-duty. Built-in BACnet communication makes this drive a direct fit for HVAC building-automation networks — no gateway or protocol converter needed. The 44 W power consumption is the drive's own draw, not the motor load; budget it for panel ventilation and UPS sizing. The drive includes a control unit and mounts as a module in frame size R0. IP20 enclosure means it's for clean indoor panels only — no washdown or dust. ## I/O and wiring note Two analog inputs and one analog output handle speed reference and feedback — 0-10 V or 4-20 mA, jumper-selectable. Four digital inputs and two digital outputs cover start/stop, fault reset, and run-status. No industrial Ethernet interface on this variant; BACnet rides on RS-485, so plan for a serial connection to the BMS controller. Frequency range is 47.5 to 63 Hz, covering 50 Hz and 60 Hz grids without reconfiguration. Power factor of 0.98 is typical for a diode-front-end drive; no active PFC stage, so harmonic content is standard for this class.","metaTitle":"ABB 3AXD50001110079 ACH180 Micro Drive, 0.75 kW, BACnet","metaDescription":"ABB ACH180-04S-04A8-2 micro drive, 0.75 kW / 1 Hp, 4.8 A, 200-240 V, 3-phase, IP20, BACnet, active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 240V"],"specifications":{"Altitude":"2000 m","Includes":"Control unit","Frame Size":"R0","Power Factor":"0.98","Analog Inputs":"2","Frequency (f)":"47.5 ... 63 Hz","Mounting Type":"Module","WEEE Category":"5. Small Equipment (No External Dimension More Than 50 cm)","Analog Outputs":"1","lifecycle_stage":"current","Number of Phases":"3-phase","Enclosure Type NEMA":"Open Type","Input Voltage (Uin)":"200 ... 240 V","Degree of Protection":"IP20","Apparent Power Output":"1.9 kV·A","Communication Protocol":"BACNET","Power Consumption (@Pcons)":"44 W","Number of Digital In/Outputs":"4 / 2","Number of Hardware Interfaces":"Industrial Ethernet 0","Output Power, Normal Use (Pn)":"0.75 kW","Output Current, Normal Use (In)":"4.8 A","Output Power, Heavy-Duty Use (PhD)":"0.55 kW","Output Current, Heavy-Duty Use (IhD)":"3.2 A","Output Power, Light-Overload Use (PlD)":"0.75 kW","Output Current, Light-Overload Use (IlD)":"4.6 A","Technical UL/Output Power, Normal Use (UL)":"1 Hp","Technical UL/Output Current, Normal Use (UL)":"4.6 A","Technical UL/Output Power, Heavy-Duty Use (UL)":"0.75 Hp","Technical UL/Output Current, Heavy-Duty Use (UL)":"3.7 A","Technical UL/Output Power, Light-Overload Use (UL)":"1 Hp","Technical UL/Output Current, Light-Overload Use (UL)":"4.6 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.abb.com/global/en/products/3axd50001110079","alternativesUrl":"https://aoctrl.com/api/mcp/products/3AXD50001110079/alternatives.json"},"ai":{"faq":[{"question":"What communication protocol does this drive support?","answer":"BACnet over RS-485. No industrial Ethernet interface is fitted on this variant."},{"question":"What is the altitude rating?","answer":"Rated for installation up to 2000 m without derating."},{"question":"What is included with the drive?","answer":"The drive includes a control unit. Frame size is R0, module mounting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/abb/3AXD50001110079","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/abb/3AXD50001110079 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}