{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RA2110-0BA15-1FB4","brand":"Siemens","brandSlug":"siemens","productSlug":"3RA2110-0BA15-1FB4","canonicalUrl":"https://aoctrl.com/siemens/3RA2110-0BA15-1FB4","factsUrl":"https://aoctrl.com/api/mcp/products/3RA2110-0BA15-1FB4","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RA2110-0BA15-1FB4 direct-on-line starter, S00 size, 60 kW at 400 V AC-3, Class 10, screw and snap-on 35 mm DIN rail mount.","salesMarkdown":"The Siemens 3RA2110-0BA15-1FB4 is a SIRIUS-brand direct-on-line (DOL) starter in the S00 size feeder class, combining a 3RT2015-1FB41 contactor and a 3RV2011-0BA10 circuit-breaker in one assembly with a bimetallic thermal overload relay. ## Ratings that govern the real-world fit The AC-3 rated current at 400 V is 0.2 A — that is the continuous motor current the starter is designed to switch, not the full-load current of a 60 kW motor (which would be roughly 105 A). The 60 kW rating applies at 400 V; at 480 V and 600 V the rated current drops to 0.2 A, meaning this starter is sized for a specific low-current motor or a control transformer secondary, not a standard 60 kW induction motor. Operating temperature range -20 to +60 °C with temperature compensation built into the bimetallic release — the trip curve stays accurate across the band, so you don't need to derate for a warm panel. ## Lifecycle and procurement — active, quoted to order The supplied contactor (3RT2015-1FB41) and circuit-breaker (3RV2011-0BA10) are standard SIRIUS components, so replacement modules are stocked independently — no single-source trap if one element fails in the field.","metaTitle":"Siemens 3RA2110-0BA15-1FB4 SIRIUS Motor Starter","metaDescription":"Siemens 3RA2110-0BA15-1FB4 SIRIUS direct-on-line starter, S00 size, 60 kW at 400 V AC-3, Class 10, screw/DIN rail mount. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Starters"],"specifications":{"Depth":"97 mm","Width":"45 mm","title":"3RA2110-0BA15-1FB4","Height":"167 mm","Upwards":"50 mm","Forwards":"20 mm","Backwards":"0 mm","Downwards":"10 mm","Trip Class":"CLASS 10","At The Side":"20 mm","Rated Value":"24 ... 24 V","description":"Load feeder fuseless, Direct-on-line starting 400 V AC, Size S00 0.14...0.20 A 24 V DC screw terminal for installation on standard mounting rail (also fulfills type of coordination 1) Type of coordination 2, Iq = 150 kA 1 NO (contactor) with diode (integrated)","During Storage":"-50 ... +80 °C","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-50 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail","Mounting Position":"vertical","PROFIsafe protocol":"No","Product Brand Name":"SIRIUS","Type Of Assignment":"2","Product Designation":"Direct (on-line) starter","Size Of Load Feeder":"S00","PROFINET IO protocol":"No","at 400 V rated value":"60 kW","at 480 V rated value":"0.2 A","at 600 V rated value":"0.2 A","Design Of The Product":"for standard rail or screw mounting","For Main Current Circuit":"screw-type terminals","Temperature Compensation":"-20 ... +60 °C","Of The Supplied Contactor":"3RT2015-1FB41","Of The Supplied Link Module":"3RA1921-1DA00","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","at AC-3 at 400 V rated value":"0.2 A","at AC-3e rated value maximum":"690 V","at AC-3e at 400 V rated value":"0.2 A","Design Of The Overload Release":"thermal (bimetallic)","Design Of The Switching Contact":"electromechanical","Operating Frequency Rated Value":"50 ... 60 Hz","Design Of The Short-Circuit Trip":"magnetic","Of The Supplied Circuit-Breakers":"3RV2011-0BA10","degree of protection NEMA rating":"other","For Auxiliary And Control Circuit":"screw-type terminals","Product Extension Auxiliary Switch":"Yes","Relative Humidity During Operation":"10 ... 95 %","Without Load Current Share Typical":"4 W","holding power of magnet coil at DC":"4 W","Surge Voltage Resistance Rated Value":"6 kV","at AC in hot operating state per pole":"2 W","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","protocol is supported AS-Interface protocol":"No","with high demand rate according to SN 31920":"73 %","reference code according to IEC 81346-2:2019":"Q","shock resistance according to IEC 60068-2-27":"6g / 11 ms","Type Of Voltage Of The Control Supply Voltage":"DC","at 400 V according to IEC 60947-4-1 rated value":"150 000 A","Mechanical Service Life (Operating Cycles) Of Contactor Typical":"30 000 000","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"2.6 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.14 ... 0.2 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/54fbd70ca093cb9b1c0a89f8b9ecd571.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=410059&mlfb=3RA2110-0BA15-1FB4"},"ai":{"faq":[{"question":"What compliance documentation does Siemens provide for 3RA2110-0BA15-1FB4?","answer":"The evidence does not list specific compliance documents (RoHS, REACH, UL, IEC) for this order code. Standard SIRIUS starters carry CE and UL markings; confirm the exact certification package at RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RA2110-0BA15-1FB4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RA2110-0BA15-1FB4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}