{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RA2110-0GA15-1AP6","brand":"Siemens","brandSlug":"siemens","productSlug":"3RA2110-0GA15-1AP6","canonicalUrl":"https://aoctrl.com/siemens/3RA2110-0GA15-1AP6","factsUrl":"https://aoctrl.com/api/mcp/products/3RA2110-0GA15-1AP6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RA2110-0GA15-1AP6 non-fused motor starter, direct starter, size S00, 3-pole, 690 V AC, Class 10 thermal bimetallic overload, snap-on DIN rail.","salesMarkdown":"## Size S00 non-fused motor starter — what it packs The 3RA2110-0GA15-1AP6: This is a Siemens SIRIUS 3RA2 non-fused motor starter, a direct starter combining a contactor and a thermal bimetallic overload relay in one unit. It ships with the contactor 3RT2015-1AP61 and the circuit breaker 3RV2011-0GA10 already linked via a link module 3RA1921-1DA00. The operating frequency range is 50 to 60 Hz. The short-circuit trip is magnetic, providing fast clearing on high faults. ## Panel fit — 45 mm wide, snap-on DIN rail Width is 45 mm, depth 97.1 mm, height 167.2 mm — size S00 footprint. Snap-mounts onto DIN rail or can be screw-mounted with an additional push-in lug. Mounting position is vertical. Clearance requirements: 20 mm upwards, 10 mm downwards, 9 mm at the side. No forward or backward clearance needed. This fits tightly in a standard 600 mm deep enclosure with room for wiring ducts. Operating temperature range -20 to +60 °C, storage -50 to +80 °C. Pollution degree 3, surge voltage resistance 6 kV — suitable for industrial control panels with moderate contamination. Supplied as a complete starter assembly: contactor, overload relay, and circuit breaker pre-linked. The auxiliary switch option is available (product extension auxiliary switch: Yes).","metaTitle":"Siemens 3RA2110-0GA15-1AP6 SIRIUS Motor Starter, Size S00","metaDescription":"Siemens 3RA2110-0GA15-1AP6 SIRIUS non-fused motor starter, size S00, 3-pole, 690 V AC, Class 10 thermal overload. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Motor Starters"],"specifications":{"Depth":"97.1 mm","Width":"45 mm","title":"3RA2110-0GA15-1AP6","Height":"167.2 mm","Upwards":"20 mm","Forwards":"0 mm","Backwards":"0 mm","Downwards":"10 mm","Trip Class":"CLASS 10","At The Side":"9 mm","Rated Value":"690 V","description":"Fuseless motor starter Direct start 600VAC Size S00 0.45-0.63A 220/240VAC 50/60HZ screw connection For screw mounting Or 35 mm rail-mounting Type of coordination 2 IQ = 150 KA Also full fills type Of coordination 1 1NO (contactor)","During Storage":"-50 ... +80 °C","lifecycle_stage":"current","During Operation":"-20 ... +60 °C","During Transport":"-55 ... +80 °C","Fastening Method":"Snap-mounted to DIN rail or screw-mounted with additional push-in lug","Mounting Position":"vertical","Product Brand Name":"SIRIUS","Type Of Assignment":"2","Degree Of Pollution":"3","Product Designation":"non-fused motor starter 3RA2","Size Of Load Feeder":"S00","at 400 V rated value":"180 W","at 50 Hz rated value":"187 ... 242 V","at 500 V rated value":"180 W","at 60 Hz rated value":"192 ... 264 V","at 690 V rated value":"250 W","Design Of The Product":"direct starter","Of The Supplied Contactor":"3RT2015-1AP61","Of The Supplied Link Module":"3RA1921-1DA00","Size Of The Circuit-Breaker":"S00","at AC-3 rated value maximum":"690 V","Design Of The Overload Release":"thermal (bimetallic)","Design Of The Switching Contact":"electromechanical","Operating Frequency Rated Value":"50 ... 60 Hz","Design Of The Short-Circuit Trip":"magnetic","Of The Supplied Circuit-Breakers":"3RV2011-0GA10","Product Extension Auxiliary Switch":"Yes","Surge Voltage Resistance Rated Value":"6 kV","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"Yes","apparent holding power of magnet coil at AC":"4.8 VA","number of NO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"6g / 11 ms","at 400 V according to IEC 60947-4-1 rated value":"153 000 A","at 500 V according to IEC 60947-4-1 rated value":"100 000 A","at 690 V according to IEC 60947-4-1 rated value":"100 000 A","operational current at AC-3 at 400 V rated value":"0.6 A","Type Of Electrical Connection For Main Current Circuit":"screw-type terminals","Inductive Power Factor With The Holding Power Of The Coil":"0.25","Mechanical Service Life (Operating Cycles) Of Contactor Typical":"30 000 000","Response Value Current Of Instantaneous Short-Circuit Trip Unit":"8.19 A","insulation voltage with degree of pollution 3 at AC rated value":"690 V","Type Of Connectable Conductor Cross-Sections For Main Contacts Stranded":"0.5 ... 4 mm², 2x (0.75 ... 2.5 mm²)","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.45 ... 0.63 A","Connectable Conductor Cross-Section For Main Contacts Finely Stranded With Core End Processing":"0.5 ... 2.5 mm²"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9d95519b0109f5a573375983e46c25bf.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=241171&mlfb=3RA2110-0GA15-1AP6"},"ai":{"faq":[{"question":"What is the panel footprint of 3RA2110-0GA15-1AP6?","answer":"Width 45 mm, depth 97.1 mm, height 167.2 mm. It snap-mounts onto DIN rail with 20 mm clearance above and 10 mm below."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RA2110-0GA15-1AP6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RA2110-0GA15-1AP6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}